0 3 6 9 12 15
15
12
9
6
3
Mini Orange
Discharge flow [l/h]
Pu
mp
in
g
he
ad
[m]
230 V
4.1 Device specifications
4.2 Capacity diagram
Q
Electric connection:
230 V, 50/60 Hz
Q
Electric capacity:
0.17 A / 16 W
Q
Max. discharge flow:
12 l/h (with a pumping head of 0 m)
2 Intended use
3 Structure
4 Technical data
The profi-air condensate pump has been designed for use with the profi-air 180 flat ventilation unit only and ensures the reliable
discharge of condensate. The profi-air condensate pump is directly connected to the control of the profi-air 180 flat ventilation unit.
Depending on the operating mode of the ventilation unit (A or B), it must always be installed on the exhaust air / fresh air side.
The profi-air condensate pump consists of a pump to discharge small amounts of condensate. The condensate pump is controlled
via a float switch. This ensures that the pump only operates if there is condensate. The delivery includes all parts to connect the
condensate pump power and condensate lines to the ventilation unit.
Q
Max. pumping head:
10 m
Q
Max. suction head:
1 m
Q
Noise level:
25 dB(A) (with a distance of 1 m)
Installation / operating instructions – profi-air 180 flat condensate pump