Establish the water connection.
11.20
Check the water connection for leaks.
11.21
Plug the manual actuator if need be.
12. Function
12.1
Pull the manual actuator.
• The water will flow.
☞
The valve is not self-closing!
12.2
Place the manual actuator back in its start position.
• The water stops flowing.
13. Maintenance and care
Check the emergency shower once a month to make sure that it is in working order.
(Guidelines for Laboratories BGI/GUV-I 850-0)
As a measure for the prevention of microbiological contamination, it is recom-
mended that you replace the fill water in the fitting at shorter intervals by opening the
valve.
Use suitable cleaning agents which do not attack the tap in a proper manner and
rinse with water after use. High-pressure cleaners must not be used for cleaning.
14. Troubleshooting
If you cannot rectify a fault or if it is not in the list, please contact our customer
service department!
15. Spare parts
Description
Order No.
Ball valve . . . . . . . . . . . . . . . . . . . . . 2030025020
☞
Other spare parts on request; see the wall bracket for material numbers.
Fault
Cause
Remedy
Water does not flow
– Water supply interrupted
➯
Restore it
Manual actuator is
catching
– Ball valve not correctly aligned
➯
Align it
– Pull rod or manual actuator bent
➯
Straighten it
– Ball valve stiff
➯
Replace it
Body shower is
dripping
– Ball valve defective
➯
Replace it