15. Thermal disinfection
This fitting offers thermal disinfection to reduce the risk of a legionella infection.
Warning!
Personal protective measures (scald protection) must be implemented for the
duration of the thermal disinfection. This might include cordoning off the shower
facilities.
Failure to observe this instruction can result in injuries due to scalding.
The operator is responsible for the execution, monitoring, and logging (room,
tapping point, date, time, temperature and duration).
The manufacturer does not accept any liability for claims by third parties relating to
the improper execution of thermal disinfection on the part of the operator.
☞
At the factory, the thermal disinfection function is set so that the fitting cools down for
1 minute after a 5 minute application time.
☞
Thermal disinfection can only be triggered using the remote control.
You can adjust the thermal disinfection parameters using the remote control (not part
of the scope of delivery; see Accessories,
chapter 20
).
An application time of 3, 5, 10, 15, or 20 minutes can be chosen for the thermal
disinfection process. During the application time, water flows without interruption for
2 minutes; the water then flows in pulses until the end of the application time (water
and energy saving function). The cooling time can be set to 0, 1, 3, 5, or 10 minutes.
16. Adjusting the cleaning switch-off
You can activate the cleaning switch-off with the remote control (not part of the
scope of delivery, see Accessories,
chapter 20
) or directly on the fitting.
Cleaning switch-off on the fitting
16.1
Hold your hand around 10 cm from the sensor for 3 seconds.
16.2
Between the 3rd and 5th flashing of the LED, remove your hand from the range of
the sensor.
• The LED does not flash.
16.3
After between 3 and 10 seconds, hold your hand around 10 cm from the sensor
again.
16.4
Once the LED has flashed three times, remove your hand from the range of the
sensor.
• The fitting will be switched off for 3 minutes.
• The LED flashes in a 10 second cycle.
☞
If you hold your hand around 10 cm from the sensor for at least 3 seconds, the fitting
will be reactivated before the 3 minutes has expired.