6. Technical Specifications
7. ID (11200)
8. Dimensions
9. Installation Example
Wall mounting, side view
Installation element, front view
10. Assembly Instructions
Warning!
• Operate the product only with safety extra low voltage (SELV). Do not earth the
components.
• The power supply (not included in the scope of delivery, see accessories,
) must be set up outside of the wet area, in a separate room.
• Secure the electric connection with an earth leakage circuit breaker (RCD).
Failure to observe can mean risk of death or material damage, e. g. from electric
shock or fire.
Before supplying power to the fittings, install the system cables (not included in
scope of delivery, see Accessories,
) in a conduit (to be supplied by
customer) and loop through.
Warning!
Operate this valve only in conjunction with the correct grit filter.
Failure to observe can lead to a damaged fitting.
☞
Important!
Before installing, flush the pipes in compliance with DIN 1988.
Check the direction of flow.
Minimum flow pressure:
1.0 bar
Recommended flow pressure:
1–5 bar
Maximum operating pressure:
10 bar
Calculation flow rate:
0.3 l/s
Flush flow rate:
0.3–0.7 l/s
Operating voltage:
24 V DC
Operating voltage:
7 W
Type of protection:
Electronics IP 68, solenoid valve IP 40