IN
– VA10
- 27 -
© Future Products Group
Refrigeration
cont.
VISAIR CABINETS - SERVICING
FPG Settings
Note that the following settings are Dixell factory defaults. Refer to the
Specification section for the correct FPG settings for your cabinet.
Dixell Default
Settings
Label
Name
Range
Default Setting
Set
Set point
LS÷ US
-5.0
Hy
Differential
0,1÷25.5°C/ 1÷ 255°F
2.0
LS
Minimum set point
-50°C÷SET/-58°F÷SET
-50.0
US
Maximum set point
SET÷110°C/ SET ÷ 230°F
110
Ot
Thermostat probe calibration
-12÷12°C /-120÷120°F
0.0
P2P
Evaporator probe presence
n=not present; Y=pres.
Y
OE
Evaporator probe calibration
-12÷12°C /-120÷120°F
0.0
P3P
Third probe presence
n=not present; Y=pres.
n
O3
Third probe calibration
-12÷12°C /-120÷120°F
0
P4P
Fourth probe presence
n=not present; Y=pres.
n
O4
Fourth probe calibration
-12÷12°C /-120÷120°F
0
OdS
Outputs delay at start up
0÷255 min
0
AC
Anti-short cycle delay
0 ÷ 50 min
1
rtr
P1-P2 percentage for regulation
0 ÷ 100 (100=P1 , 0=P2)
100
CCt
Continuous cycle duration
0.0÷24.0h
0.0
CCS
Set point for continuous cycle
(-55.0÷150,0°C) (-67÷302°F)
-5
COn
Compressor ON time with faulty probe
0 ÷ 255 min
15
COF
Compressor OFF time with faulty probe
0 ÷ 255 min
30
CF
Temperature measurement unit
°C ÷ °F
°C
rES
Resolution
in=integer; dE= dec.point
dE
Lod
Probe displayed
P1;P2
P1
rEd2
X-REP display
P1 - P2 - P3 - P4 - SEt - dtr
P1
dLy
Display temperature delay
0 ÷ 20.0 min (10 sec.)
0
dtr
P1-P2 percentage for display
1 ÷ 99
50
tdF
Defrost type
EL=el. heater; in= hot gas
EL
dFP
Probe selection for defrost termination
nP; P1; P2; P3; P4
P2
dtE
Defrost termination temperature
-50 ÷ 50 °C
8
IdF
Interval between defrost cycles
1 ÷ 120 ore
6
MdF
(Maximum) length for defrost
0 ÷ 255 min
30
dSd
Start defrost delay
0÷99min
0
dFd
Displaying during defrost
rt, it, SEt, DEF
it
dAd
MAX display delay after defrost
0 ÷ 255 min
30
Fdt
Draining time
0÷120 min
0
dPo
First defrost after start-up
n=after IdF; y=immed.
n
dAF
Defrost delay after fast freezing
0 ÷ 23h e 50’
0.0
ALc
Temperature alarms configuration
rE= related to set; Ab = absolute
Ab
ALU
MAXIMUM temperature alarm
Set÷110.0°C; Set÷230°F
110
ALL
Minimum temperature alarm
-50.0°C÷Set/ -58°F÷Set
-50.0
Continued on next page
Summary of Contents for Visair IN-VA10-A004
Page 1: ...Open Front Food Drinks Cabinet AS NZS ...
Page 35: ...IN VA10 35 Future Products Group MECHANICAL DRAWINGS Inline Visair IN VA10 A004 ...
Page 36: ...Part No 25553 Rev J November 2017 36 Visair Refrigerated Cabinets Inline Visair IN VA10 A005 ...
Page 37: ...IN VA10 37 Future Products Group ...
Page 38: ...Part No 25553 Rev J November 2017 38 Visair Refrigerated Cabinets ...