Refrigerated Well GN Series
Controller Settings
GN SERIES REFRIGERATED WELL
-
SPECIFICATIONS
Changes from
Dixell Defaults
The following table specifies the controller settings which differ from the Dixell
default values.
Parameters not listed in this table should remain at the default values specified
in the
XR40CZ Parameters
listed in the
Servicing
section.
XR40CX Settings
Parameter
Description
Settings for Models
Units/Range
IN-
GNC0
8
Set
Set Point
-6
degC
Hy
Differential
6
degC
AC
Anti Short Cycle Delay
2
Min
C0n
Comp On Time - Faulty Probe
4
Min
C0F
Comp Off Time - Faulty Probe
6
Min
dtE
Defrost Terminate Temp
3
degC
IdF
Interval Between Defrosts
2
Hrs
dFd
Display During Defrost
DEF
rt, it, Set, DEF
ALU
Maximum Temperature Alarm
12
degC
AFH
Differential For Temp Alarm
8
degC
Ald
Temperature Alarm Delay
60
Min
AP2
Probe For High Discharge Temp Alarm
nP
nP, P1, P2, P3, P4
i1P
Digital input polarity
oP
oP
i1F
Digital input configuration
bAL
EAL,Bal,pal,dor,dEF,AU
S,Htr,ES
did
Digital input alarm delay
1
Min
Nps
Number activations of pressure switch
1
0-15