IN 5H08/12/15/18
- 17 -
© Future Products Group
Location
HEATED CABINETS
-
INSTALLATION
Ventilation
The vent located on the rear of the cabinet must never be obstructed. If
obstructed the cabinet may overheat and cause an electrical malfunction.
Before use, operate the cabinet for 1-2 hours to remove any fumes or odours,
which may be present.
Access
The cabinet should also be positioned so the operating panel and shelves are
easily reached for loading and unloading.
Power Supply
HEATED CABINETS
-
INSTALLATION
Voltage Rating
Before connecting to the power supply, check that the local supply is correct to
that shown on the rating plate, located on the rear of the cabinet.
Supply Current
Ratings for
1200, 1500 &
1800 Cabinets
The current draw of the 1200, 1500 and 1800 heated cabinets is more than 10
Amps, and they cannot therefore be supplied by a standard 10 Amp plug and
socket.
A warning label, adjacent to the supply lead, states the maximum current rating
for the cabinet. No plug is fitted to the supply lead, which must therefore be
terminated appropriately by the installing electrician.
CONNECTING THESE CABINETS TO A STANDARD 10 AMP POWER SUPPLY MAY
DAMAGE YOUR WIRING AND POSSIBLY CAUSE A FIRE.
Isolation
If the cabinet is not connected by a plug and socket, but is hard wired to the
mains supply, a means of isolation must be provided.
The isolator or plug should be accessible after the cabinet is installed.
Earthing
THIS APPLIANCE MUST BE EARTHED/GROUNDED
The cabinet should be earthed via the earth lead in the
mains cable.
In addition, an equipotential earth bonding terminal is
provided, to allow the cabinet to be bonded to a building
surge earth or adjacent equipment.