FoxESS AC1 Series User Manual Download Page 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H1/AC1 SERIES 

 

 

User Manual 

 

In order to prevent improper operation before use, please carefully read this 
manual. 

 

Summary of Contents for AC1 Series

Page 1: ...H1 AC1 SERIES User Manual In order to prevent improper operation before use please carefully read this manual...

Page 2: ...rotection 10 4 6 General Data 10 5 Installation 11 5 1 Check for Physical Damage 11 5 2 Packing List 11 5 3 Mounting 12 6 Electrical Connection 14 6 1 PV Connection For Hybrid Only 14 6 2 Battery Conn...

Page 3: ...n this document as described below Danger Danger indicates a hazardous situation which if not avoided will result in death or serious injury Warning Warning indicates a hazardous situation which if no...

Page 4: ...re to specified cooling requirements Unauthorized removal of necessary protections improper use incorrect installation and operation may lead to serious safety and shock hazards or equipment damage Be...

Page 5: ...ty regulations Do not connect the ground terminals of the unit in series in case of a multiple installation This product can cause current with a DC component where a residual current operated protect...

Page 6: ...nverter and the meter distribution system SPD test impulse D1 for signal line according to EN 61632 1 All DC cables should be installed to provide as short a run as possible and positive and negative...

Page 7: ...enerator the power generated will be used to supply the local loads firstly then export to the public grid The redundant power will charge the battery Force time use Priority battery load grid when ch...

Page 8: ...itted to set the connection Item Description A DC Switch For Hybrid Only B PV1 For Hybrid Only C PV2 For Hybrid Only D Battery Connector E METER CT RS485 F Ethernet G BMS H DRM I BACK UP J USB K AC Co...

Page 9: ...input A input B A A 15 B 15 Max inverter backfeed current to the array mA 0 MPPT voltage range V 80 550 80 550 80 550 80 550 80 550 Start up voltage V 75 75 75 75 75 No of MPP trackers 2 2 2 2 2 Strin...

Page 10: ...distortion THDi rated power 3 AC INPUT Max AC power VA 3000 4000 Bypass 3680 4000 Bypass 4600 5000 Bypass 5000 5000 Bypass 6000 6000 Bypass Max AC current A 31 8 34 9 43 7 45 5 54 6 Rated grid voltage...

Page 11: ...onsumption W Idle 3 STANDARD Safety IEC62109 1 2 IEC62040 EMC EN 61000 6 1 EN 61000 6 2 EN 61000 6 3 Certification G98 G99 AS4777 2 2015 EN50549 1 CEI 0 21 VDE AR N 4105 NRS097 2 1 and so on 4 6 Gener...

Page 12: ...I J P Object Quantity Description Object Quantity Description A 1 Inverter I 1 Earth terminal B 1 Bracket J 1 Communication connector C 4 PV connectors for hybrid only 2 positive 2 negative K 1 Produ...

Page 13: ...in the range of 25 C to 60 C The slope of the wall should be within 5 The wall hanging the inverter should meet conditions below 1 Solid brick concrete or strength equivalent mounting surface 2 Invert...

Page 14: ...e the bracket on the wall and mark the position of the 5 holes from bracket Drill holes with electric drill make sure the holes are at least 50mm deep and then tighten the expansion tubes Insert the e...

Page 15: ...connected should be less than 600V and operating voltage should be within the MPPT voltage range Note Please choose a suitable external DC switch if the inverter does not have a built in DC switch Wa...

Page 16: ...rresponding crimping pliers and crimp the contact Insert pin contact through the cable nut to assemble into back of the male or female plug When you feel or hear a click the pin contact assembly is se...

Page 17: ...Separate the connectors by hand 6 3 Grid Connection Step 1 Grid String Connection H1 AC1 series inverters are designed for single phase grid Voltage range is 220 230 240V frequency is 50 60Hz Other t...

Page 18: ...local cable type and color for actual installation A BACK UP Wiring Separate the BACK UP plug into three parts as below Hold middle part of the female insert rotate the back shell to loosen it detach...

Page 19: ...e cable nut with rubber insert from the back shell Slide the cable nut and then the back shell onto the cable Push the threaded sleeve into the socket tighten up the cap on the terminal Push the threa...

Page 20: ...r working status performance etc and update that information to monitoring platform the WiFi LAN GPRS device is available to purchase from your local supplier Connection steps 1 For GPRS device Please...

Page 21: ...ve Compatible Meter type DDSU666 CHINT SDM230 EASTRON CT This inverter has an integrated export management function To enable this function a power meter or CT must be installed The CT should be clamp...

Page 22: ...PC or other monitoring devices Meter optional The inverter has integrated export limitation functionality To use this function a power meter or a CT must be installed For Meter installation please in...

Page 23: ...ated power DRM3 Do not consume at more than 75 of rated power and source reactive power if capable DRM4 Increase power consumption subject to constraints from other active DRMs DRM5 Do not generate po...

Page 24: ...he below situation 1 For data transmission It can transmit the inverter data from inverter to PC or other monitoring equipment 2 For monitoring It can transmit the inverter data from inverter to Foxes...

Page 25: ...side of the cable connector Step 3 Insert the cable connector into BMS port at the bottom of inverter and screw it tightly COM ESTOP Close the inverter Generator Connect the generator and start up it...

Page 26: ...or then insert the network cable through the cable connector Step 3 Crimp the cable with a Rj45 plug which is inside of the cable connector Step 4 Insert the cable connector into COM port at the botto...

Page 27: ...er Derating for Voltage Variation Volt Watt Mode Details of how to enable this mode are contained in the Advanced Configuration Guide which can be accessed at our website at https www foxess com 6 6 E...

Page 28: ...nd EPS switching of inverters improve maximum EPS loads capacity maximum bypass current is 60A 2 When the grid power is off ensure that the Back up load power is lower than the inverter s maximum outp...

Page 29: ...er for the first time the country code will be set by default to the local settings Please check if the country code is correct Set the time on the inverter using the button or by using the APP The in...

Page 30: ...s follow update master H1_master_vx xx bin update slave H1_slave_vx xx bin update manager H1_manager_vx xx bin Note vx xx is version number Warning Make sure the directory is in accordance with above...

Page 31: ...e inverter is in fault mode C Blue The inverter is normally connected to the battery D Green The inverter is in normal state E Function button Up button Move cursor to upside or increase value Down bu...

Page 32: ...tips to identify and solve most problems that can occur 9 1 Alarm List Fault Code Solution Grid Lost Fault Grid is lost System will reconnect if the utility is back to normal Or seek help from us if n...

Page 33: ...us voltage out of range detected by software Disconnect PV grid and battery then reconnect Or seek help from us if not go back to normal state Bat Volt Fault Battery voltage fault Check if the battery...

Page 34: ...range detected by hardware Disconnect PV grid and battery then reconnect Or seek help from us if not go back to normal state HW Pv Cur Fault PV input current high detected by hardware Disconnect PV gr...

Page 35: ...mosfet is fail Disconnect PV grid and battery then reconnect Or seek help from us if not go back to normal state Bat Boost Fault The battery boost circuit mosfet is fail Disconnect PV grid and battery...

Page 36: ...back to normal state RDSP SPI Fault The communication between master and slave is fail Disconnect PV grid and battery then reconnect Or seek help from us if not go back to normal state RDSP Smpl Faul...

Page 37: ...r Bms HW Protect Battery hardware under protection Please contact battery supplier BmsCircuit Fault Bms hardware circuit fault Please contact battery supplier Bms Insul Fault Battery insulation fault...

Page 38: ...ence to perform these tests The data should be recorded in an equipment log If the device is not functioning properly or fails any of the tests the device has to be repaired For safety check details r...

Page 39: ...ent box that meets the following requirements Suitable for loads more than 30 kg Contains a handle Can be fully closed 10 3 Storage and Transportation Store the inverter in dry place where ambient tem...

Page 40: ...not plagiarize partially or fully copy including software etc and no reproduction or distribution of it in any form or by any means is permitted All rights reserved FOXESS CO LTD WUXI BRANCH Add No 1...