Installing a NetIron MLX Series Router
December 2008
© 2008 Foundry Networks, Inc.
3-27
Figure 3.21 Connecting a Power Cord to the Power Supply in a NetIron MLX-16 Chassis
WARNING:
If the installation requires a different power cord than the one supplied with the device, make sure
you use a power cord displaying the mark of the safety agency that defines the regulations for power cords in your
country. The mark is your assurance that the power cord can be used safely with the device.
4.
For information about powering on the system, see “Powering-On the Power Source” on page 3-50.
Connecting DC Power to a NetIron MLX-16 Chassis
You can use a DC power source for the NetIron MLX-16 chassis. This is supported through use of a DC-to-DC
power supply. DC power must be supplied at 48 V and 30 A. The DC-to-DC supply provides the DC power to the
chassis at 12 V and 100 A.
WARNING:
The procedure in this section is for qualified service personnel.
To connect a DC power source, you must use the following directions:
1.
Use a flat-blade screwdriver to remove the two screws holding the transparent cover over the power supply
lugs.
Figure 3.22 The NetIron MLX-8 and NetIron MLX-16 DC Power Supply
Lift Handle
Lift Handles
Power Cord
Cord Retainer
Ground Point
DC IN
DC OUT ALM
Screws Holding
Transparent Cover
Screws Holding
Transparent Cover
Screws Holding
Power Lugs