Goodrive20 Series VFD
Installation guidelines
-13-
Chapter 3 Installation guidelines
The chapter describes the mechanical installation and electric installation of the VFD.
Only qualified electricians are allowed to carry out what described in this
chapter. Please operate as the instructions in Chapter 1 "Safety
precautions". Ignoring these may cause physical injury or death or
damage to the devices.
Ensure the power supply of the VFD is disconnected during the operation.
Wait for at least the time designated after the disconnection if the power
supply is applied.
The installation and design of the VFD should be complied with the
requirement of the local laws and regulations in the installation site. If the
installation infringes the requirement, our company will exempt from any
responsibility. Additionally, if users do not comply with the suggestion,
some damage beyond the assured maintenance range may occur.
3.1 Mechanical installation
3.1.1 Installation environment
The installation environment is the safeguard for a full performance and long-term stable
functions of the VFD. Check the installation environment as follows:
Environment
Conditions
Installation site Indoor
Environment
temperature
-10°C
–+50°C, and the temperature changing rate is less than
0.5°C/minute.
If the ambient temperature of the VFD is above 40°C, derate 1% for every
additional 1°C.
It is not recommended to use the VFD if the ambient temperature is above
50°C.
In order to improve the reliability of the device, do not use the VFD if the
ambient temperature changes frequently.
Please provide cooling fan or air conditioner to control the internal
ambient temperature below the required one if the VFD is used in a close
space such as in the control cabinet.
When the temperature is too low, if the VFD needs to restart to run after a
long stop, it is necessary to provide an external heating device to increase
the internal temperature; otherwise, damage to the devices may occur.
Humidity
RH≤90%
No condensation is allowed.
Summary of Contents for GD20-004G-2
Page 1: ......