background image

The  boiler  must  be  installed  in  a  fixed  loca-

tion  and  only  by  specialized  and  qualified

firms  in  compliance  with  all  instructions

contained in this manual.

Furthermore,  the  installation  must  be  in

accordance  with  current  standards  and

regulations.

2.1

BOILER ROOM 

AND VENTILATION

The 

“LOGO” 

version  boilers  with  less  than

35  kW  power  can  be  installed  in  domestic

environments when simply replacing or in a

plant  room  complying  with  current  stan-

dards  In  rooms  where  open  chamber  gas

appliances are installed, it is important that

at  least  as  much  air  at  least  as  much  air

can  arrive  as  required  by  normal  combu-

stion  of  the  gas  consumed  by  the  various

appliances. 

The  minimum  distance  between  the  boiler

and inflammable materials has to be  

200

mm. Consequently, it is necessary to make

openings  in  the  walls  for  the  air  inlet  into

the rooms (around 2 m

3

/h for each kW of

heat input). These openings must meet the

following requirements:

–Have  a  total  free  section  of  at  least  6

cm

2

for  every  kW  of  heat  input,  with  a

minimum of 100 cm

2

.

–They  must  be  located  as  close  as  possi-

ble  to  floor  level,  not  prone  to  obstruc-

tion  and  protected  by  a  grid  which  does

not reduce the effective section required

for the passage of air.

2.2

CONNECTING UP SYSTEM

Before proceeding to connect up the boiler,

you are recommended to make the air cir-

culating  in  the  piping  in  order  to  eliminate

any  foreign  bodies  that  might  be  detrimen-

tal to the operating efficiency of the applian-

ce. It is always advisable to put intercepting

sluice  gates  on  the  C.H.  flow  and  return

tubes.  The  gas  connection  must  be  made

using  seamless  steel  pipe  (Mannesmann

type),  galvanized  and  with  threaded  joints

provided with gaskets, excluding three-piece

connections,  except  for  initial  and  end  con-

nections.  Where  the  piping  has  to  pass

through  walls,  a  suitable  insulating  sleeve

must be provided. 

When  sizing  gas  piping,  from  the  meter  to

the boiler, take into account both the volume

flow  rates  (consumption)  in  m

3

/h  and  the

relative density of the gas in question. 

The  sections  of  the  piping  making  up  the

system  must  be  such  as  to  guarantee  a

supply  of  gas  sufficient  to  cover  the  maxi-

mum  demand,  limiting  pressure  loss

between the gas meter and any apparatus

being used to not greater than:

–1.0 mbar for family II gases (natural gas);

–2.0  mbar  for  family  III  gases  (butane  or

propane).

94

2

INSTALLATION

1

2

3

4

2

5

6

7

8

9

10

11

12

15

13

14

Fig. 3/b

“LOGO 32/80 OF” version

KEY

1 Control panel
2 Non return valve
3 Air vent valve
4 D.H.W. circulating pump
5 C.H. circulating pump
6 Manual filling group
7 Magnesium anode
8 D.H.W. tank drain cock
9 D.H.W. tank

10 Boiler drain cock

11 Burners manifold
12 Pilot burner
13 Gas valve

14 Gas pressure switch
15 Ignition transformer

Summary of Contents for LOGO 22 OF

Page 1: ...e boiler is set for operation for the type of gas supplied Check that the flue pipe for the outlet of the products of the combustion is unobstructed Make sure that any shutoff valves are open Make sur...

Page 2: ...50 D H W tanks LOGO 32 50 OF 32 80 OF central heating and D H W production electronic ignition and modulation natu ral draught Follow the instructions given in this manual for the correct installation...

Page 3: ...tank unit BT150 version CONNECTIONS M C H flow 3 4 M R C H return 3 4 M E D H W inlet 1 2 M G Gas connection 3 4 M U D H W outlet 1 2 M C Re circulation 1 2 F S1 Safety valve drain 1 2 F S2 D H W tank...

Page 4: ...D H W circulating pump 10 C H circulating pump 11 Gas valve 12 Burners 13 Non return valve 14 Burners manifold 15 Water pressure transducer 16 Boiler drain cock 17 D H W expansion vessel 18 D H W safe...

Page 5: ...40 80 40 80 40 80 40 80 D H W setting range C 10 60 10 60 10 60 10 60 Category II2H3P II2H3P II2H3P II2H3P Type B11BS B11BS B11BS B11BS Smokes temperature C 108 110 116 119 Smokes flow gr s 18 5 23 2...

Page 6: ...W expansion vessel 5 Manual filling group 6 D H W tank 7 D H W tank drain cock 8 Boiler drain cock 9 Burners manifold 10 Pilot burner 11 C H circulating pump 12 Gas valve 13 Gas pressure switch 14 Saf...

Page 7: ...connect up the boiler you are recommended to make the air cir culating in the piping in order to eliminate any foreign bodies that might be detrimen tal to the operating efficiency of the applian ce...

Page 8: ...t this operation check that the filling tap is closed 2 5 FLUE The flue for the atmospherical expulsion of the combustion products from natural draught appliances must meet the following requirements...

Page 9: ...nector ends 3 dama ges irreparably the control panel Before the connection make sure that there is no voltage 2 6 2 Logica Remote Control connection fig 6 pos B The electrical systems must be in com p...

Page 10: ...on the inspection control and cleaning flange of the tank 2 6 5 Wiring diagram J7 J5 J4 J3 J2 KEY TR Transformer 230 24V TRA Ignition transformer P C H circulating pump PB D H W circulating pump EA I...

Page 11: ...through a window contact Anti bacterial 2 7 1 Installation The unit must be installed in the main living room For installation follow the assembly instructions inserted in the package At this point w...

Page 12: ...until it finds the optimum switch off time 59 60 SETTING THE HOT WATER SERVICE PARAMETERS Reduced hot water temperature value Hot water service filling The hot water may be set to a reduced temperatu...

Page 13: ...witch over to reduced pre set value of the ambient temperature 3 With an external contact it is possible to switch over to reduced pre set value of the antifreeze ambient temperature short circuit 0 0...

Page 14: ...eginning when the plant is cold and in the subsequent startings This is so to avoid ignitions and switching off with very short intervals that may in particular be found in plants with high losses At...

Page 15: ...ntinuous jump spark from the electrode is noted despite the pilot burner being lit After 20 seconds the sparking stops the burner goes off and the block signal lights up The cable of the detector elec...

Page 16: ...PERTURA TA 6 SB 11 SB 12 CIRCUITO CON VALVOLE DI ZONA NOTA I rel vengono impiegati solo nel caso le valvole di zona siano prive di micro L N TA TA1 VZ R VZ1 R1 NOTA PER VERSIONI SOLO RISCALDAMENTO Sos...

Page 17: ...g potentiometer knob on the maximum value Using a 10 wrench turn the nut 3 to find the maximum pressure as shown in Table 2 to reduce the pressure turn the nut anti clockwise to increase the pres sure...

Page 18: ...ENANCE Carry out the cleaning of the generator in the following way fig 18 Remove the electricity supply to the boi ler and close the gas supply tap Dismantle the gas group completely Dismantle the li...

Page 19: ...erature always with the primary circuit controlled between 80 C and 70 C During the entire duration of the testing the hot water taps must remain open After verifying the combustion the boiler should...

Page 20: ...C and the yellow led of the hot water will light up at the same time In the versions with storage capacity when there is no request for hot water service and heating the leds and are off the operatin...

Page 21: ...ed Technical Service between April and September The boiler comes with an electricity supply cable which in case of replacement must be requested only from SIME FAULT FINDING Starting failure fig 3 If...

Page 22: ...hts up To attempt to start the boiler again unscrew the cover of the thermostat and reset the button under neath After 10 minutes from the resetting the boiler will automatically restart For an immedi...

Page 23: ...he boiler will function by placing the selector on the o position obviously without consequent control of the room temperature The functioning instructions are inside the lid fig 9 Every setting or mo...

Page 24: ...l lowing list of items one after the other are displayed The thermo feeler continues to function independently of the display Day hour room temperature External temperature Hot water service temperatu...

Page 25: ...ity boiler unit temperature desired for hot water service at reduced level To have access to the reduced hot water service temperature parameter press the and keys at the same time for at least 5 seco...

Page 26: ...rature set in parameter 3 1 standard Hot water according to the daily heating programme In the comfort periods of the heating the temperature of the boiler unit is regulated at the value set via para...

Page 27: ...ode Current values Display and setting of the gradient of the heating characteristics curve When the room temperature set is not reached choose the gradient indicated in point 2 7 3 Display of the cur...

Page 28: ...oning by acting on the filling tap of the boiler fig 4 Plant overpressure Call the Authorised Technical Service for assistance Thermostat safety interception Call the Authorised Technical Service for...

Reviews: