97
2.6.3
External temperature sensor
connection (fig. 6 pos. C)
The cables must be placed in compliance
with the specifications for safety low voltage
EN 60730. For lengths up to 25 m use
cables with a section of 0.25 mm
2
and for
lengths up to 50 m use cables with a section
of 0.5 mm
2
. To have access to the connector
of the boiler (3) remove the control panel
cover and electrically connect the external
temperature feeler to the terminals SE (8-9).
2.6.4
D.H.W. sensor “BT130 - BT150”
connection
The
“BT130 - T150”
tanks come with a
D.H.W. sensor (SB) to be connected to the
J2 connector (3 fig. 6)
When the tank unit is matched to boilers
“22 OF - 32 OF”
, introduce the sensor in
the sheaf on the inspection, control and
cleaning flange of the tank.
2.6.5
Wiring diagram
J7
J5
J4
J3
J2
KEY
TR
Transformer 230 - 24V
TRA Ignition transformer
P
C.H. circulating pump
PB
D.H.W. circulating pump
EA
Ignition electrode
ER
Sensing electrode
EV1 Gas valve coil
EV2 Gas valve coil
TS
Safety stat 100°C
PG
Gas pressure switch
TF
Smoke safety device
M
Modulator
TPA Water pressure transducer
SM
C.H. sensor (blue)
SB
D.H.W. sensor
SE
External sensor (optional)
CR
Logica Remote Control (optional)
TA
Room stat
OP
Time programmer
Note: When connecting the room stat
remove the bridge between the termi-
nals 5-6.
vers. LOGO 22 OF - 32 OF
CONNECTOR SPARE PART CODES:
J2
code 6278613
J3
code 6278642
J4
code 6278628
J5
code 6278643
J7
code 6278626
vers. LOGO 32/50 - 32/80 OF
CONNECTOR SPARE PART CODES:
J2
code 6278613
J3
code 6278629
J4
code 6278628
J5
code 6278627
J7
code 6278636
Fig. 7