background image

TURNING OFF BOILER

To turn off the boiler set the switch to “OFF”

and close the gas-feeding pipe tap if the boi-

ler  remains  inoperative  for  a  long  period

(fig. 1).

SYSTEM FILLING 

(fig. 4)

Check periodically that the thermomanome-

ter shows a reading of between 1 - 1.2 bar

(1), with the system cold. 

If the pressure drops below the blue scale

(1), the boiler will not operate. 

To  re-set  the  pressure,  rotate  the  char-

ging  valve  to  the  anticlockwise  direction

until  the  thermomanometer  reading  re-

enters the blue scale (1). 

Once  this  operation  is  completed,  make

sure the tap is closed. 

In  case  the  pressure  goes  above  the  limit,

empty  the  exceeding  pressure  by  opening

the pressure relief valve on any radiator. 

The blue part of the scale (2) indicates the

working pressure range with the heating in

operation.  Should  the  pressure  exceed  the

values  of  the  blue  scale  (2),  causing  the

safety valve intervention, call the authorized

technical staff.

"25 OF - 30 OF" SMOKE

SAFETY DEVICE

This  is  a  safety  device  against  possible

smoke emission into the ambience. 

The safety device switches off the gas valve

when  the  return  of  the  smokes  into  the

ambience  is  continuous  and  then  dange-

rous.  The  intervention  of  this  device  locks

out the appliance because the burner is not

ignited.  In  this  case,  turn  the  rotary  switch

to the

position (fig. 3) nd release it imme-

diately, then turn it back to the summer

or winter

.

Should  the  boiler  “lock  out”  again,  you

must call the authorized technical staff.

GAS CONVERSION

Should  it  be  necessar y  t o  conver t  the

appliance  to  a  different  gas  from  the  one

for  which  the  boiler  has  been  equipped,

approach the technical staff.

CLEANING AND MAINTENANCE

At  the  end  of  each  heating  season,  it  is

essential  to  have  the  boiler  thoroughly

checked and cleaned out.

Preventive  maintenance  and  checking  of

the  efficient  operation  of  the  equipment

and  safety  devices  must  be  carried  out

exclusively  by  the  authorized  technical

staff. 

The  boiler  is  supplied  with  an  electric

cable.  Should  this  require  replacement,

contact  exclusively  with  the  authorized

technical staff.

TIME PROGRAMMER (optional)

With  the  selector  in  the 

“AUTO”

position,

the  boiler  operation  is  regulated  according

to  the  temperatures  set  for  the  program-

med time periods. 

During  start-up,  the  second  selector  must

be in the 

“RUN”

position. Programming:

Setting the time

(fig. 5)

Move the selector to 

. To change the

hour on the display, press the

“h”

button,

to  change  the  minutes,  press  the 

“m”

button.

To  set  the  day,  press  button 

“1...7”

until

the arrow points to the correct day (1 =

Monday ....... 7 = Sunday).

Setting the programme

(fig. 6)

The  programmer  has  8  start-up  pro-

grammes and 8 shutdown options.

To make programming easier, 3 start-up

and  3  shutdown  programmes  have

already  been  set  up  for  each  day  of  the

week, as follows:

NOTE:Programmes  from  7  to  16  are  not

pre-set.

To select programmes other than those

pre-set,  move  the  selector  to  the 

“P”

position:  “0:00  1”  will  appear  on  the

display:  the  first  three  figures  indicate

the hour and minutes, the fourth figure is

the number of the programme. 

Programmes with odd numbers are swit-

ch-on  times  (daytime  temperature)  and

are indicated on the display by a light bulb

symbol. Programmes with even numbers

indicate  the  temperature  reduction

(night). 

Use button 

“1...7”

to select the day of the

week (from 1 to 7), or the period (1 ÷ 5,

6 - 7; 1 ÷ 6; or every day if the program-

me  has  to  be  repeated  every  day  of  the

week).  Set  the  hour  and  minutes  using

buttons 

“h”

and 

“m”

The  operation  in  memorized  by  pressing

button 

“P”

93

Fig. 3

SCALA COLORE AZZURRO

APRE

0

30

60

90

120

bar

°

C

0

3

4

1

SCALA COLORE BLU

0

30

60

90

120

bar

°

C

0

3

4

1

Fig. 4

Programa

Hora de

Hora de

encendido

apagado

1

06.00

-

2

-

09.00

3

12.00

-

4

-

14.00

5

18.00

-

6

-

22.00

Fig. 5

BLUE SCALE (1)

BLUE SCALE (2)

OPEN

Summary of Contents for FORMAT 25 BF

Page 1: ...for the outlet of the products of the combustion is unobstructed and has been pro perly installed Make sure that any shutoff valves are open Make sure that the system is charged with water and is tho...

Page 2: ...h electronic ignition and modulation natural draught FORMAT 25 BF 30 BF with electronic ignition and modulation room sealed forced draught The instructions given in this manual are provided to ensure...

Page 3: ...1 1 CH setting range C 40 80 40 80 40 80 40 80 D H W setting range C 40 60 40 60 40 60 40 60 D H W flow rate EN 625 l min 10 5 12 7 10 5 12 7 Continuous D H W flow rate t 30 C l min 11 1 13 6 11 1 13...

Page 4: ...n pump 11 Expansion vessel 12 Safety valve 13 Boiler discharge 14 Flowmeter 15 Thermomanometer 16 Automatic by pass 17 D H W filter 18 C H return cock optional 19 C H flow cock optional 20 D H W cock...

Page 5: ...her makes optional The kit code 8093900 is supplied comple te with mounting instructions 2 3 CONNECTING UP SYSTEM Before proceeding to connect up the boiler you are recommended to make the air cir cul...

Page 6: ...smokes coo ling in particular if located outside the building or in unheated ambiences Be set at an adequate distance from combustible or easily inflammable mate rial by means of an air gap or suitabl...

Page 7: ...han 78 KEY 1a b Coaxial duct kit code 8084805 2a Extension L 1000 code 8096100 2b Extension L 500 code 8096101 3 Vertical extension L 200 with take off point code 8086908 4 Supplementaty 90 elbow code...

Page 8: ...H2O vers 30 For head losses in the fittings refer to Table 2 79 TABLE 2 Accessories 80 Head loss mm H2O 25 version 30 version Inlet Outlet Roof outlet Inlet Outlet Roof outlet 90 elbow MF 0 30 0 40 0...

Page 9: ...xceed 7 00 mm H2O 25 vers and 11 00 mm H2O 30 vers When calculating the lengths of pipe take into account the parameters given in the Table 2 80 Fig 13 120 80 160 KEY 1 Sponge rubber gasket 125 95 2 F...

Page 10: ...emove the front panel and the two screws that anchor the control panel to the sides see point 4 7 The panel will tilt forward at a sufficient angle to allow access to the components To remove the prot...

Page 11: ...as valve coil EV2 Gas valve coil EA Ignition electrode ER Sensing electrode A SIT 503 control box TS 100 C safety stat TF Smoke stat FL Flowmeter P Circulation pump VP Divertor valve TAG Antifreeze st...

Page 12: ...nals 22 23 2 10 5 25 OF 30 OF wiring diagram with HONEYWELL control box Fig 20 b KEY EV1 Gas valve coil EV2 Gas valve coil EA Ignition electrode ER Sensing electrode A HONEYWELL S4565CF control box TS...

Page 13: ...read with the temperature set on the potentio meter The adjustment range is between 40 and 60 C When the heating flow sensor is at 75 C the electronic limiter will trip and switch off the burner The b...

Page 14: ...uent re ignition will depend on a tempe rature difference of 3 C detected by the SM sensor heating flow sensor ATTENTION It is essential that the opera tions described above be carried out by authoriz...

Page 15: ...Y DEVICE This is a safety device against possible smoke emission into the ambience 14 fig 3 The safety device goes into action by blocking operation of the gas valve when the return of the smoke into...

Page 16: ...tore TA 22 23 L N TA TA1 P R P1 R1 CIRCUITO CON VALVOLE DI ZONA CIRCUITO CON POMPE DI ZONA Fig 26 KEY TA TA1 Zone room stat VZ VZ1 Zone gas valve R R1 Zone relay CR CR1 Zone microvalve or relay contac...

Page 17: ...mini mum values are factory set Consequently they must not be altered Only when you switch the appliance from one type of gas supply methane to another butane or propane it is permitted to alter the...

Page 18: ...ater potentiometer knob set to the maximum the hot water tap turned on and the burner lit hold nut 3 locked in place and simulta neously turn nut 2 using a fixed 7 wrench to identify the minimum pres...

Page 19: ...of the boiler Unscrew the connection 1 and the lock nut 5 Remove the bracket and the expansion vessel 4 NOTE Before refilling the system using a pressure gauge attached to the valve 3 make sure that...

Page 20: ...he control box is faulty replace it Gas valve fails to modulate in D H W and C H modes The sensor is interrupted replace it The modulator has a break in winding replace it Check that the current to th...

Page 21: ...ure that the requi red temperature is kept constant With the rotary switch in the winter position once the boiler has reached the value set on the heating potentiome ter it will start to modulate in a...

Page 22: ...entive maintenance and checking of the efficient operation of the equipment and safety devices must be carried out exclusively by the authorized technical staff The boiler is supplied with an electric...

Page 23: ...the clock display together with an indication of the incorrect program me To cancel all the programmes move the selector to the P position and press buttons 3 and 5 simultaneously Setting the SKIP fun...

Reviews: