Refrigeration charges
Refrigeration replacement requirements
Non-contaminated refrigerant removed from any Follett refrigeration system can be recycled and returned to
the same system after completing repairs. Recycled refrigerant must be stored in a clean, approved storage
container. If additional refrigerant is required, virgin or reclaimed refrigerant that meets ARI standard 700-88 must
be used.
In the event of system contamination (for example, a compressor burn out, refrigerant leak, presence of non-
condensibles or moisture), the system must be repaired, evacuated and recharged using virgin or reclaimed
refrigerant that meets ARI standard 700-88.
Follett Corporation does not approve of recovered refrigerants. Improper refrigeration servicing procedures will
void the factory warranty.
16
R404A icemaker charge specifications
Model Line
Run
Charge
825
0 – 50 ft (0 – 15.2m)
8 lbs (3.6kg)
50 – 75 ft (15.2 – 22.9m)
9 lbs (4.1kg)
75 – 100 ft (22.9 – 30.5m)
10 lbs (4.5kg)
100 ft+ (30.5m+)
Consult factory