13
HARMONY • RIDE Technology
self-contained
Horizon ice machines can be installed undercounter/in-cabinet to fi ll bins or dispensers using RIDE technology. Care must
be taken to ensure proper cabinet venting to avoid recirculation of hot air. Improper venting can cause ice machine out-
ages.
22.25"
(57 cm)
min.
24.5"
(62 cm)
min.
drain
cabinet door
ice transport tube
Horizon
ice machine
supplied
grilles
minimum 1/4" per foot
(2 cm per meter)
pitch toward icemaker
secure to prevent dips
and traps from forming
water
electric
18" (46 cm)
min.
see dispenser
specification
sheet for
installation
requirements
12" (30 cm) minimum
between icemaker
and dispenser
must mate directly
to air intake gasket
exhaust
air in
Horizon ice machine
completed installation with
gasket and door in place –
side view
Front
locating
cutout
24.5" (62 cm) min.
22.25"
(57 cm)
minimum
cutout for supplied air intake grille
supplied air
intake grille
18"W x 14"H (46 cm x 36 cm)
bottom of
ice machine
side of
ice machine
cutout
2"
(50 mm)
2"
(50 mm)
cabinet door
door & gasket
must mate
directly
1. The supplied exhaust grille must be located at least
18" (46 cm) from the supplied air intake grille (exhaust air must
not recirculate with intake air).
2. Cabinet interior must be open to allow for unrestricted exhaust
air fl ow.
3. Ice transport tube needs minimum 1/4" per foot (2 cm per
meter) pitch toward ice machine and should be secured to
prevent dips and traps from forming.
4. Cabinet door must mate directly to air intake
gasket.
5. Cabinet interior must provide a minimum clear
space of
24.5" deep (62 cm) by 22.25" high (57 cm).
6. Cutout for supplied grilles must meet minimum size
requirements shown above.
7. Utilities should be conveniently located as shown.
Undercounter installation detail – Horizon 700 series (continued)