DSX-602 CableAnalyzer
Users Manual
54
Notes
Set the reference only after the testers are at an
ambient temperature between 10 °C and 40 °C
(50 °F and 104 °F).
The tester will not let you set the reference if the
patch cord is longer than 30 cm (12 in).
You can also set the reference with a 50
patch
cord
3
On the home screen, select a coaxial cable test.
4
On the home screen, tap
TOOLS
, then tap
Set Reference
.
5
On the
SET REFERENCE
screen tap
TEST
.
BK179.EPS
Figure 21. Reference Connections for Tests on Coaxial Cabling
DSX-CHA003
COAX ADAPTER
DSX-CHA003
COAX ADAPTER
Coaxial adapter
with F connector
adapter
30 cm (12 in) 75
coaxial patch cord
Coaxial adapter
with F connector
adapter