Fluidwell F112-P Manual Download Page 1

 
 
 

 

F112-P 

FLOW RATE INDICATOR / TOTALIZER 

with linearization, analog and pulse outputs

 

 
 
 

 
Signal input flowmeter: pulse, Namur and coil. 
Signal outputs: (0)4-20mA / 0-10V ref. flow rate and pulse ref. total. 
Options: Intrinsically safe, Modbus communication, external reset and 
backlight. 

 

 

F-Series - Field mounted indicators for safe and hazardous areas.  

More info: www.fluidwell.com/fseries

 

Summary of Contents for F112-P

Page 1: ...ignal input flowmeter pulse Namur and coil Signal outputs 0 4 20mA 0 10V ref flow rate and pulse ref total Options Intrinsically safe Modbus communication external reset and backlight F Series Field m...

Page 2: ...to the general waste system or into a landfill At the end of its life equipment shall be disposed of according to the local regulations regarding waste of the electrical and the electronic equipment P...

Page 3: ...connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the F112 P or connected instruments A note ind...

Page 4: ...option 17 3 1 11 Explanation of Setup menu A Others 17 4 Installation 18 4 1 General directions 18 4 2 Installation surrounding conditions 18 4 3 Dimensions Enclosure 19 4 4 Installing the hardware 21...

Page 5: ...arsh industrial surroundings ability to process all types of flowmeter signals transmitting possibilities with analog pulse and communication outputs Flowmeter input This manual describes the unit wit...

Page 6: ...light to show the process information status and alarm messages The display refresh rate is programmed in the setup menu At a key press the display refresh rate will switch to FAST for 30 seconds When...

Page 7: ...AND FUNCTIONS In general the F112 P operates in the operator mode The shown information depends on the settings which are made in the setup menu The signal from the connected sensor is processed by th...

Page 8: ...999 The unit and number of decimals are shown according to the settings for the total Low battery alarm Only use original batteries Original batteries can be ordered at the manufacturer The use of un...

Page 9: ...is possible to prevent access to the setup menu with a password A password may be required to enter the setup menu Without this password access is denied 3 1 HOW TO PROGRAMM THE F112 P The setup menu...

Page 10: ...and the setting UNIT When you do not want to save the change wait for approximately 20 seconds or press and hold the PROG ENTER key for approximately 3 seconds Action Result Remark 1 Momentarily pres...

Page 11: ...ational shelf 5 FLOWMETER 51 SIGNAL npn npn lp reed reed lp pnp pnp lp namur coil hi coil lo 8 1 DC 12 DC 24 DC 6 LINEARIZE 61 freq m factor 1 0 1 9999 9 Hz 0 000001 9 999999 62 freq m factor 2 0 1 99...

Page 12: ...4 When you recalculate and reprogram a new K Factor the history for accumulated total is not correct anymore because the accumulated total is not recalculated For future reference best practice is to...

Page 13: ...ernal power supply is required to supply the backlight 3 1 5 EXPLANATION OF SETUP MENU 4 POWER MANAGEMENT When used with the internal battery option type PB PC the user can expect reliable measurement...

Page 14: ...COIL LO Low sensitive coil input min 80 mVpp Normal sensitivity 8 1 DC Active pulse input detection level 8 2V DC 3K9 max 10KHz External power required 12 DC Active pulse input detection level 12V DC...

Page 15: ...V in most applications at zero flow The number of decimals shown depend upon setup 23 The engineering units time e g L min are dependent upon setup 21 and 22 RATE MAX 73 Enter here the flow rate at wh...

Page 16: ...99 01 filter disabled filter disabled filter disabled filter disabled 02 0 1 sec 0 2 sec 0 4 sec 0 7 sec 03 0 2 sec 0 4 sec 0 6 sec 1 2 sec 05 0 4 sec 0 7 sec 1 1 sec 2 1 sec 10 0 7 sec 1 4 sec 2 2 se...

Page 17: ...and the Modbus communication protocol description for a detailed explanation SPEED 91 This setting is used to set the Baudrate ADDRESS 92 This setting is used to set the communication address for the...

Page 18: ...SURROUNDING CONDITIONS Take the relevant IP classification of the enclosure into account see identification plate Even an enclosure rated for IP67 TYPE 4 X should NEVER be exposed to strongly varying...

Page 19: ...5 mm 0 6 deeper rear cover 75 mm 2 95 130 mm 5 12 112 mm 4 40 120mm 4 72 M20 x 1 5 PG9 PG9 30mm 30mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm M20 x 1 5 M20 x 1 5 M20 x 1 5 25mm 25mm 1 2 NPT 0 9 3x 1 2...

Page 20: ...36 120 mm 4 72 HD HK HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm...

Page 21: ...a non metallic enclosure could invalidate isolation 4 4 1 GENERAL INSTALLATION GUIDELINES The F112 P that came with a power module type PM 110V 230V AC or type PD PF with an option OR the relays can h...

Page 22: ...onal and local electrical codes To ground the field mounted unit the PE conductor must be connected to the PE stud which is located in the metal back cover as indicated in the image below To connect t...

Page 23: ...ing screws that attach the cover to the back panel Type PM 110 230V AC The PE connection in the metal back panel is made with a serrated washer a terminal a washer and a screw The PE connection to the...

Page 24: ...STIC GRP ENCLOSURE The PE connection The F112 P in a GRP enclosure meets the requirements of class 2 double insulated Therefore the incoming PE wire is terminated with an insulating end cap Type PM 11...

Page 25: ...ly influence the battery life time It is strongly advised to use a zero power pickup such as a coil or reed switch when operating without external power It is possible to use some low power NPN or PNP...

Page 26: ...24V DC 18Vin AC 26Vin DC Type PF Power supply in 15 24V AC 20 30V DC Switch location typical Sensor Vout selection Sensor supply out A 1 2 3 4 int off off Coil 1 2V DC 1mA Reed 3V DC 1mA ext on on of...

Page 27: ...Y type AP output loop powered Connect an external power supply of 8 30VDC to these terminals or a 0 4 20mA loop Do connect the to terminal 7 and the to terminal 8 When power is applied to these termin...

Page 28: ...this option When the output is disabled a 3 5mA signal will be generated on these terminals Max driving capacity 1000 Ohm 30VDC This option can be used with a battery powered unit but the life time o...

Page 29: ...input signal type has to be selected in the flowmeter setup read chapter 3 Sine wave signal Coil The F112 P is suitable for use with flowmeters which have a coil output signal Two sensitivity levels...

Page 30: ...tion level of 50 of the supply voltage please refer to active signals Fig 20 Terminal connections PNP signal input typical Active signal 8 2V 12V and 24V If a sensor gives an active signal read chapte...

Page 31: ...Fig 24 Terminal connections External reset typical Terminal 26 31 type CB CH CI CT communication RS232 RS485 TTL option For connections refer to figure Overview of terminal connectors Standard config...

Page 32: ...ron steel is excluded For EPL Da the ambient temperature Ta shall not exceed 50 C Safety instructions When two or more active Intrinsically safe circuits are connected to the indicator in order to pre...

Page 33: ...ear of production This information can be looked up in the setup menu Others Fig 25 Example serial number typical Label information pulse input type F1xx XI inside and outside the enclosure Fig 26 Lab...

Page 34: ...upply connected to terminals 7 and 8 type AP The maximum values for any of those circuits are those as defined for group IIB IIIC No other active external Intrinsically safe circuits may be connected...

Page 35: ...ernal power is only available when the main external power supply is connected The sensor supply voltage is fixed 8 2V DC Set the sensor supply 1 Make the F112 P safe If applicable mind the battery po...

Page 36: ...FW_F112P_v1901_02_EN docx Page 36 5 3 CONFIGURATION EXAMPLES Fig 30 F112 P AP CT IB OT PC XI Battery powered IIB IIC IIIC...

Page 37: ...FW_F112P_v1901_02_EN docx Page 37 Fig 31 F112 P AP CT IB OT PX XI Output loop powered IIB IIC IIIC...

Page 38: ...y with the utmost care to prevent a short circuit and damage 4 Do not recharge crush disassemble incinerate heat above its rated temperature or expose the contents to water 5 Dispose of the battery in...

Page 39: ...ime Analog output signal be sure that an external power supply is connected or that the function is disabled if not in use or else it will have a major influence on the battery life time Display updat...

Page 40: ...pe HG Type HJ Type HH Type HK Dimensions 130 x 120 x 75mm 5 10 x 4 72 x 2 95 3 54 WxHxD IP67 TYPE 4 X where H turns to HS for stainless enclosures e g HA HSA Drilling 2x PG9 1x M20 Drilling 2x NPT Dri...

Page 41: ...t 15 LVD EN IEC 61010 1 ATEX IECEx EN IEC 60079 0 EN IEC 60079 11 RoHS EN 50581 IP NEMA EN 60529 NEMA 250 Flowmeter Type P npn npn lp reed reed lp pnp pnp lp namur coil hi coil lo 8 1 DC 12 DC 24 DC F...

Page 42: ...ve 24V DC transistor output max 50mA per output requires type AA PD PF or PM Type OR Isolated mechanic relay output max switch power 230V AC 0 5A requires type PF or PM Type OT Passive transistor outp...

Page 43: ...e selected pulse width and frequency Flow rate displays 0 zero while there is flow total is counting Check are the K Factor and time unit correct The unit has to count the number of pulses according t...

Page 44: ...ing using your Modbus device please read our General Modbus Communication Protocol and Modbus troubleshooting guide that are available through our website or your distributor Runtime variables PDU ADD...

Page 45: ...W uint32 1 9999999 Representation 0 000010 9999999 depending on variable 54 decimals K Factor d 54 h 0x036 40055 K Factor decimals 1 R W uint16 0 6 d 55 h 0x037 40056 number of pulses 1 R W uint16 1 2...

Page 46: ...address 1026 contain the M factor part Valid range for the frequency is 0 000 to 9999Hz Decimal point dependent on variable 1039 A value of 0 for frequency means that entry is disabled Valid range fo...

Page 47: ...FF d 147 h 0x093 40148 delay 1 r w uint16 delay between read and write command 0 65355 d 150 h 0x096 40151 index 1 r w uint16 See PDU address 0x400 d 149 h 0x095 40150 Index use 1 r w uint16 0 static...

Page 48: ...FW_F112P_v1901_02_EN docx Page 48 APPENDIX D DECLARATION OF CONFORMITY...

Page 49: ...rs Standard configuration and options 25 Fig 9 Sensor supply voltage Switch setting 26 Fig 10 Terminal connections Active output typical 26 Fig 11 Terminal connections Mechanical relay output typical...

Page 50: ...010 27 cut off 30 0 sec 3 DISPLAY 31 function total 32 light 100 4 POWER MANAGEMENT 41 LCD new 1 sec 42 battery mode operational 5 FLOWMETER 51 signal coil lo 6 LINEARIZATION 61 frequency 0 0Hz M Fac...

Page 51: ...000000 6F frequency 0 0Hz M Factor 1 000000 6G linearization disabled 6H decimals frequency 1111 1 7 ANALOG 71 output disabled 72 rate min 0000000 73 rate max 9999999 74 cut off 0 0 75 tune min 0208 7...