User Manual
E126-P-EL
Page 58
FW_E126-P-EL_M_v0301-01_EN
A.3
OUTPUT
DIGITAL OUTPUT
Function
Transmitting compensated accumulated total (scaled pulse) or input pulse retransmission
Scaled output
Output D1: max. frequency 500 Hz.
Output D5: max. frequency 4 Hz, recommended use below 0.5 Hz
Pulse length user definable between 1msec up to 10 seconds
Retransmission output Square wave output based on frequency of (sine wave or coil) input signal. Maximum frequency
10kHz with a 50% duty cycle, minimum on and off-time 50µs
Type OT
One passive transistor output (NPN) - not isolated. 300 mA – 50 V @ 25°C
Type OR
One isolated electro-mechanical relay output (NO).
Maximum resistive load: 2A @ 250 VAC / 30 VDC.
Maximum inductive load: 0.5 A (pilot duty applications).
Note 1: Requires 24 – 27 VDC and supplied via P5 - P6.
Note 2: Type OT remains available.
Note 3: Not used in pulse retransmission mode
ANALOG OUTPUT
Function
Transmitting compensated flowrate
Type AH
Galvanically isolated, loop powered 4 – 20 mA output
Accuracy
12 bit. Error 0.03% @ 20°C (Typical 45 ppm/°C).
Can be scaled to any desired range
Supply voltage
10 V (lift-off voltage) - 27 VDC
Max load
700 ohm @ 24 VDC (24 V – 10 V / 20 mA)
COMMUNICATION
Function
Reading display information, reading/writing all configuration settings, and data log extraction
Type CB
Modbus ASCII/RTU - RS232
Type CH
Modbus ASCII/RTU - RS485 2-wire, bus termination without resistor for low power solutions
Type CU
USB communication incl. Ex d plug (requires ¾”NPT or M25 side entry thread)
Type CX
No communication, remote configuration possible with accessory cable (ACE02)
Speed (baud)
1200 - 2400 - 4800 - 9600 - 9600HP - 19200 – 38400
Addressing
Maximum 247 addresses
A.4
OPERATIONAL
FLOW EQUATIONS
Type EL
Compensated liquid volume
Formula
where α = thermal expansion coefficient.
OPERATOR FUNCTIONS
Displayed information
●
Compensated flowrate, total and accumulated total
●
Current day total, previous day total and 15 historical day totals (compensated)
●
Actual line temperature
●
Indicating speedometer for compensated flowrate
●
Total can be reset to zero by pressing the CLEAR-key twice
TOTAL
Digits
7 digits
Unit
L, m3, US gal, igal, cf, Oil bbl, kg, ton, US ton, lb or none
Decimals
0 – 1 – 2 or 3
Note
Total can be reset to zero