Flue & Ducting Woodford Series Installation Manual Download Page 1

PLEASE RETAIN THIS GUIDE FOR FUTURE REFERENCE 

Booklet 722

 Rev 01

ISSUE DATE : 0x/0x/2018 

EN 13240:2011 +A2:2004 

WOODFORD Stove 

Installation Guide

Summary of Contents for Woodford Series

Page 1: ...PLEASE RETAIN THIS GUIDE FOR FUTURE REFERENCE Booklet 722Rev 01 ISSUE DATE 0x 0x 2018 EN 13240 2011 A2 2004 WOODFORD Stove Installation Guide ...

Page 2: ...ue Ducting has a policy of continuous product development and therefore we reserve the right to amend specifications without prior notice Due to printing cycles items or options may be described before they are generally available or after they have ceased Please check with your retailer or dealer if you are unsure about any aspect of your stove its installation or correct use Woodford Stove Insta...

Page 3: ...e Stove 5 1 Removing The Door 5 2 Removing The Throat Plate Liners 5 3 Fitting The Spigot Outlet 5 4 Fitting The Hot Plate Blanking Plate 5 5 Connecting The Spigot Outlet To The Flue System 5 6 Firebox Liner Panels 5 7 Smoke Control Areas The Clean Air Act 1993 Smoke Control Areas 5 8 Optional Accessories 6 Commissioning The Stove 6 1 Checklist Booklet 722 Page 3 4 4 5 5 6 7 8 8 9 9 9 10 10 10 11 ...

Page 4: ...ntial or incidental loss or injury however caused 2 Health Safety 2 1 Heath Safety Practice Before any installation work is undertaken consideration must be given to the Health and Safety at Work Act 1974 Safe working practices should be followed at all times Please consult health and safety guidelines for advice on handling heavy and or large items During installation ensure that adequate precaut...

Page 5: ...om the front of the appliance and 150mm either side of the edge of the appliance In most buildings with solid concrete or stone floors the requirement will be met by the floor itself but mark the hearth to ensure floor coverings are kept well away or use different levels to mark the hearth perimeter Please be aware that hot air can cause staining above the fire in a similar fashion to walls above ...

Page 6: ...te If the appliance is fitted with a draught stabiliser or if one is fitted to the flue pipe or chimney in the same room as the appliance then the permanent air entry opening or openings should be increased by 300mm2 for each kW of rated output up to 5kW and an additional 850mm2 for each kW output over 5kW If there is more than one appliance in the property then each appliance must be supplied wit...

Page 7: ... relevant Building Regulations that specify the requirements for solid fuel burning installations Suitable types of chimney include the following Masonry Chimney Built with clay or concrete liners or a chimney block system meeting Building Regulations These types of chimneys should be installed in accordance with the Building Regulations and BS EN 15287 1 2007 Factory Made Insulated Chimney Comply...

Page 8: ...y and that heat is being sucked out of the appliance and up the chimney If this is the case we recommend the fitting of a draught stabiliser in preference to a flue damper in the interest of safety and efficiency 5 Installing The Stove To make the stove easier to manoeuvre and safer we recommend you remove the following parts which can then be refitted when the stove is in its final position Liner...

Page 9: ...s dependent upon the installation requirements Fitting is simply done using the supplied M6 nuts and washers no bolts are required as studs are factory fitted to the hot plate disc Again fire cement can be used in conjunction with the self adhesive rope seal 5 5 Connecting The Spigot Outlet To The Flue System The flue pipe must be fitted inside the outlet spigot as shown in Figure 2 Failure to do ...

Page 10: ...ion can be found via https www gov uk smoke control area rules then the secondary air lever must be fitted with a restrictor plate to prevent total closure of the secondary air control A factory fitted threaded hole is positioned adjacent to the secondary air control for fitting of the supplied restrictor plate and fixing NOTE The minimum air control setting is governed in manufacture to meet the ...

Page 11: ...rson schemes please complete a Certificate of Compliance which is used for checking and reporting the installation as imposed by the Government Otherwise please ensure the installation is approved by your local building control officer Ensure a Carbon Monoxide alarm is fitted This must be between 1m to 3m from the appliance and approximately 150mm below the ceiling level A fireguard conforming to ...

Page 12: ... Haigh Avenue Whitehill Industrial Estate Stockport SK4 1NU United Kingdom www woodfordcollection co uk T 44 0 161 480 2994 Email sales flue ducting co uk DATE OF ISSUE 2018 All Woodford Stoves are manufactured in the UK WOODFORD Stove Installation Guide ...