440 V -------------------------------- TR1 tags No. 1 & 4
480 V ------------------------------- TR1 tags No. 1 & 5
2. Connect the motor supply cable (Using 4x0.75-1mm) between control board and Filter junction
box terminals. (Through flexible conduit g land)
Control board Filter Junction box
TB5 - Motor GND. wire. (Yellow/green wire) ---------------
Æ
TB5
TB6 - Motor U wire. -------------------------------------------------
Æ
TB6
TB7 - Motor V wire. -------------------------------------------------
Æ
TB7
TB8 - Motor W wire. ------------------------------------------------
Æ
TB8
IMPORTANT! Verify good connection to MOTOR GROUND.
3. Connect the flushing solenoid & differential pressure switch cable (Using 3/4x0.75mm)
Between control board and filter junction box terminals. (Through flexible conduit gland)
a.
Using 4x0.75 cable.
Control board
Filter Junction box
TB9 - Solenoid live. ----------------------------------------------
Æ
TB9
TB10 - Solenoid natural.-----------------------------------------
Æ
TB10
TB11 - differential pressure switch live. ---------------------
Æ
TB11
TB12 - differential pressure switch natural. ----------------
Æ
TB12
b.
Using standard 3x0.75mm cable.
Control board Filter Junction box
TB9 - Solenoid live. -----------------------------------------------
Æ
TB9
TB10 - Solenoid natural.------------------------------------------
Æ
TB10 & TB12 jumpered.
TB11 - differential pressure switch live. ----------------------
Æ
TB11
TB12 – no connection needed.
E.
OPERATION.
Motor synchronization must be carried out as follows :
a. Switch the [MAIN] switch to ON = 1 position and Verify that L1 [ON] indicator lights.
b. Press pushbutton [MANUAL FLUSH] momentarily and Verify that L2 [FLUSH] indicator lights
and the motor activated simultaneously.
Check the motor axis rotation (Which drives the filter dirt collector),
The rotation must be at
the same arrow label direction.
If not , switch the [MAIN] switch to OFF = 0 position , and exchange between two of the
Motor phase and check again.(e.g. Between motor connection to TB 6-7 or TB 7-8 in the control
board or in the filter junction box.)
F.
TIMERS
FUNCTION.
TP
- Differential pressure sense timer. (Factory set to 5 sec.)
Note that in case of differential pressure signal continuation the system will flush every TP
Time set.
TF
– Flush timer. (Factory set to 10 sec.)
NOTE that the practical flushing time is the time required for the hydraulic piston to
Complete its movement due to a given line pressure. In order to minimize the flushing
Time/waste of flushed water set TF respectively.
TD
– Interval flush timer. (Factory set to 10 hours & enabled - TB 13/14 shorted)
NOTE that the TD timer can be disabled by removing the short wire from TB 13/14-SET
inlets)
For more information:
WEB: FLTR.com.au PHONE: (+61) 1300 62 4020 EMAIL: [email protected] SKYPE: Purple.Engineering