StarTalk™ DTM Help for StarPac 3 System
© Flowserve Corporation
Version 1.0.0 – Printed November 1, 2013
StarPac 3 System Setup Checklist
A. Power
•
(24) VDC Power at least 100 mA.
•
Polarity correct.
•
Local display ON. If not, check power supply.
B. System Communications (if connected to a remote computer)
•
RS-485 converter properly installed or attached to computer.
•
Signal polarity correct.
•
Modbus device address set in StarPac 3 device; refer to StarPac3 IOM.
•
Start StarTalk software.
•
Configure communications in software and hardware to match. Refer to Communications
section of this manual and the on board Help in the StarTalk XP software.
•
Communications work. If not, recheck settings.
C. Calibration Checks
•
Air supply turned on.
•
Check status screens to verify system calibration; refer to software section.
•
Valve stroke calibration to remove installation and handling offsets; refer to calibration
section.
•
Verify process sensor calibration; re-calibrate if needed.
D. System Configuration; refer to Configure StarPac section for details
•
Set or verify failure modes.
•
Set or verify analog output.
•
Set or verify command and mode source.
•
Set or verify stroke limits
•
Set or verify LCD display options.
•
Check positioner response and set gain to control speed.
•
Set units.
•
Set or verify tag name.
E. Automatic PID Operation; refer to Tune PID section
•
Select process variable.
•
Input full scale range.
•
Set initial PID parameters.
•
Begin Automatic mode and tune system.
F. Other Options; refer to Monitor Operation section