background image

 

 

IPS SMART RTU ENGLISH 701-4101-01^ 6-14 

 

Page 

9

 of 

24

 

 

    

flowserve.com

 

 

provides a visual light indication if any sensors on 
the Smart RTU unit are or have been in alarm 
status.  To define the alarm limits for each sensor, 
refer to Section 5  CUSTOM CONFIGURATION 
PROGRAMMING.
 
 
The table below describes each of the different 
types of indications offered by the RTU-OVAL 
accessory. 
 

Table 4: RTU-OVAL visual alert description  

LED 

State 

Description 

GREEN 

Light 
flashes on 
for 400 
milliseconds 

Normal operation 

– all sensors are 

within acceptable limits 

RED 

Light 
flashes on 
for 400 
milliseconds 

Current alarm 

– one of the sensor 

measurements has exceeded its alarm 
limit and has not returned within the 
acceptable range 

RED & 
GREEN 

Each color 
light flashes 
on for 400 
milliseconds  

Alarm 

– one of the sensor measurements 

previously exceeded its alarm limit, but has 
now returned within the acceptable range 

 
The time period for which the RTU-OVAL lights will 
flash to indicate a past alarm event is set to 14 
days by default.  
 

3.6  Individual Sensor Alert Light (RTU-
SAL-X) Optional Accessory 

The Individual Sensor Alert Lights (RTU-SAL-X) 
are an optional accessory for the Smart RTU.  
When installed in a Smart RTU, each light 
automatically provides a visual light indication if its 
particular sensor is in alarm status.  Each sensor 
on the Smart RTU requires its own Sensor Alert 
Light.  To define the alarm limits for each sensor, 
refer to Section 5  CUSTOM CONFIGURATION 
PROGRAMMING.
 
 

3.7  Individual Backlit Sensor 
Information Display (RTU-SID-X) 
Optional Accessory 

The Individual Backlist Sensor Information Displays 
(RTU-SID-X) are an optional accessory for the 
Smart RTU.  When installed in a Smart RTU, each 
display shows the actual current applicable sensor 
reading in the predefined engineering units. 
Each sensor on the Smart RTU requires its own 
Sensor Information Display.  Refer to the Smart 
RTU test sheet to determine the engineering units 
configured for each sensor. 
 

4  MAINTENANCE 

The only field maintenance required on the Smart 
RTU is checking the battery and charging system. 

The Smart RTU can also be turned off when not in 
use for extended periods of time to conserve 
battery life. 

 

4.1  Tools required 

 

Set of SAE wrenches 

 

Phillips head screwdriver 

 

Small flat-head screwdriver 

 

Voltmeter 

 

4.2  Turning unit on/off 

To power off Smart RTU disconnect the fuse for the 
battery cables and the wires coming from the 
power supply or solar panel (refer to included 
wiring diagram to identify the correct fuse blocks).  
This will stop sensor readings and data 
transmission. 

 

To power up the Smart RTU again, simply 
reconnect the battery and power supply or solar 
panel fuses inside the enclosure (refer to included 
wiring diagram to identify the correct fuse blocks).  
This will activate sensor readings and data 
transmission at the pre-configured intervals. 

 

Figure 2: Fuses on inside of Smart RTU 
enclosure 

 

4.3  Battery Replacement 

 

EXPLOSION HAZARD: 

Do not open 

enclosure when an explosive atmosphere may be 
present.

  

The unit must be powered OFF during the 

battery installation. 

 

WARNING STATIC HAZARD:

 Wipe only with 

a damp cloth due to electrostatic discharge hazard. 
  

 The substitution of components may 

impair intrinsic safety.  

 

Summary of Contents for IPS Smart RTU

Page 1: ...llation Operation Maintenance Multiple Sensor Input and Wireless Transmitting Unit PCN 26999987 6 14 E Original Instructions These instructions must be read prior to installing operating using and mai...

Page 2: ...ACCESSORY 8 3 6 INDIVIDUAL SENSOR ALERT LIGHT RTU SAL X OPTIONAL ACCESSORY 9 3 7 INDIVIDUAL BACKLIT SENSOR INFORMATION DISPLAY RTU SID X OPTIONAL ACCESSORY 9 4 MAINTENANCE 9 4 1 TOOLS REQUIRED 9 4 2 T...

Page 3: ...Electromagnetic Compatibility EMC Pressure Equipment Directive PED and Equipment for Potentially Explosive Atmospheres ATEX Where applicable the Directives and any additional Approvals cover importan...

Page 4: ...his sign is not a safety symbol but indicates an important instruction in the assembly process 1 6 2 Personnel qualification and training All personnel involved in the operation installation inspectio...

Page 5: ...90 noncondensing Power requirement 24VDC 110VAC or 220VAC Channel output power 24VDC Sensor Input Types Vibration overall 4 20mA signal Thermocouples RTD PT100 PT1000 Pressure 4 20mA Discrete Oil Wat...

Page 6: ...ate precautions Exposure of these cells to high temperatures or fire can cause the cells to vent and or rupture These cells do not contain dangerous substances The reaction products are inorganic and...

Page 7: ...he Smart RTU unit should come pre configured for your specific use 3 1 Options and model numbers The Smart RTU can either have wireless data transmission enabled or disabled In both settings certain a...

Page 8: ...d to a Smart RTU it automatically logs data from all sensors at the preconfigured log interval Data from the VB 103 TAM and the log interval can be reviewed utilizing an IPS Dock connected to a PC The...

Page 9: ...ation Display RTU SID X Optional Accessory The Individual Backlist Sensor Information Displays RTU SID X are an optional accessory for the Smart RTU When installed in a Smart RTU each display shows th...

Page 10: ...RATION PROGRAMMING This section is optional As long as your specific application was communicated to the factory prior to shipment the Smart RTU unit is pre configured for your specific use Errors in...

Page 11: ...l display accessories simply place Smart RTU in a vertical position 3 Insert sensor wire s into the proper terminals 4 Ensure battery is connected to battery terminal wires and then connect the batter...

Page 12: ...hen use the mounting holes on the back of the Smart RTU enclosure to bolt the unit to the pieces of unistrut Next if applicable install the solar panel facing the equator with a tilt from horizontal o...

Page 13: ...isual Alert Light RTU OVAL Individual Sensor Alert Light s RTU SAL X and Individual Sensor Information Display s RTU SID X are already installed on the Smart RTU unit if ordered They do not require an...

Page 14: ...IPS SMART RTU ENGLISH 701 4101 01 6 14 Page 14 of 24 flowserve com 7 2 Drawings Figure 8 AC Powered Smart RTU drawing...

Page 15: ...IPS SMART RTU ENGLISH 701 4101 01 6 14 Page 15 of 24 flowserve com Figure 9 Solar Powered Smart RTU...

Page 16: ...IPS SMART RTU ENGLISH 701 4101 01 6 14 Page 16 of 24 flowserve com Figure 10 Smart RTU with RTU OVAL RTU SAL and RTU SID accessories...

Page 17: ...IPS SMART RTU ENGLISH 701 4101 01 6 14 Page 17 of 24 flowserve com Figure 11 Inside of Smart RTU with RTU OVAL RTU SAL and RTU SID accessories...

Page 18: ...1 Open the power supply solar panel fuse 2 Read battery level using voltmeter connected to battery terminals If the battery level is below 11V replace the battery according to instructions in section...

Page 19: ...stored to the VB 103 TAM unit this could have several causes Incorrect loose sensor cable connections Loose VB 103 TAM connection Low battery on VB 103 TAM Incorrect VB 103 TAM log interval configurat...

Page 20: ...power supply will need to be replaced Contact the Flowserve factory for assistance b Solar Panel confirm the power coming out of the power regulator is 12VDC or higher If there is no output from the...

Page 21: ...uirements Part 1 General Requirements EN 55011 2009 Industrial scientific and medical equipment Radio frequency disturbance characteristics Limits and methods of measurement Class A Group 1 EN 61000 3...

Page 22: ...atmospheres Part 11 Equip protection by intrinsic safety i Explosive Atmospheres Part 26 Equipment with equipment protection level ELP Ga EN 61241 0 2006 Elec App for use in presence of combustible du...

Page 23: ...onstrate that the product meets the requirements of the Directives has been compiled by the signatory below and is available for inspection by the relevant enforcement authorities Signed _____________...

Page 24: ...owserve Corporation Pump 5215 North O Connor Blvd Suite 2300 Irving Texas 75039 5421 USA Telephone 1 972 443 6500 Fax 1 972 443 6800 Europe Middle East Africa Flowserve FSG Italy Worthington S r l Via...

Reviews: