INSTALATION, OPERATION & MAINTENANCE 

MANUAL 

FOR

 

PA-1001A Series 

SIGNAL CONDITIONER 

& CONVERTORS 

Summary of Contents for PA-1001A Series

Page 1: ...PA1001A 7 02 Page 1 of 11 INSTALATION OPERATION MAINTENANCE MANUAL FOR PA 1001A Series SIGNAL CONDITIONER CONVERTORS...

Page 2: ...d subsequent conditioning provides a pulse output signal The output signal of the PA1001A series have a square pulse wave form each pulse representative of an actuator rotor blade gear tooth turbine b...

Page 3: ...rigger level Trigger Sensitivity 4 millivolt RMS minimum NOTE At 4mV frequency range 10 Hz to 3KHz Input Impedance 40K Ohms nominal Maximum Input Signal 600 Volts RMS Maximum Distance From Pickup To P...

Page 4: ...the PA1001A preamplifier It is recommended that the PA1001A be installed on or near the pickup coil to assure optimum performance INSTALLATION The Model PA1001A should be placed in a convenient locati...

Page 5: ...esired pulse output as follows Pulse Output Type HD1 Jumper Configuration Open Collector JP2 Square Wave to Vin JP1 and JP2 TTL CMOS JP1 JP2 and JP3 0 10 VDC Square Wave JP1 JP2 and JP4 6 Install pick...

Page 6: ...Figure 2 3 Connect the Pulse output wire to Terminal 3 and connect the Pulse common to Terminal 4 see Figure 2 4 Set Jumper HD2 see Figure 3 to the MAG position 5 Configure Jumper HD1 see Figure 3 to...

Page 7: ...f 11 Analog Output Option 1 For current output wire two conductor shielded cable to terminals 2 common and 3 current output 2 For voltage output wire two conductor shielded cable to terminals 2 common...

Page 8: ...red pickup coils to be used as the input Input Coil Type HD2 Setting RF RF Magnetic MAG LIN RAW PULSE A two position jumper that is used to select the desired Pulse train Pulse Type JP1 Setting Raw pu...

Page 9: ...alue i e 0 VDC at zero RPM COARSE RANGE ADJ A dual in line DIP switch which is located on the PCA 121 board which is used to perform a coarse range adjustment for the input frequency range VFS SELECTI...

Page 10: ...rent equal to SET SPAN Iterate above steps until no change is observed FOR VOLTAGE OUTPUT NOTE For proper adjustment of the voltage output First Perform calibration of the current output Connect a dig...

Page 11: ...0 VDC 2 110 VAC 50 60 Hz 3 220 VAC 50 60 Hz Ordering Information For PCA 121 For Digi Pulse Pickup PCA 121 B 1 w Series Mounting C Explosion Proof Enclosure B Nema 4X Enclosure P Panel Mount Operating...