FlowCon AHU Wafer Installation And Operation Instruction Download Page 1

INSTALLATION AND OPERATION INSTRUCTION

AUTOMATIC BALANCING VALVE

WITH PRE-SET INSERT

FlowCon AHU Wafer 50-80mm

        

1W95000 

04/2016

FlowCon International assumes no responsibility 

for mistakes, if any, in any printed material.

Denmark 

Dubai 

USA 

Singapore 

www.flowcon.com

- 1 -

FlowCon AHU Wafer 50-80mm, 2”-3”

Figure 1

Install the 

FlowCon AHU Wafer

 as called 

for in the design drawings. INSTALL THE AHU 

WAFER HOUSING WITH THE FLOW DIREC-

TIONAL ARROW POINTING IN THE CORRECT 

DIRECTION.

The 

FlowCon AHU Wafer

 (Model Nos. 

F386.X.X.B) is available for end connections of 

DIN steel flanges from PN10 and up. For valve 

sizes 2½” and 3”  ANSI steel flanges from class 

150 and up are available and for size 2” ANSI 

steel flanges class 300 are to be used. Flanges 

are not supplied by FlowCon. 

Extended

 pressure/temperature fittings 

(p/t 

plugs) are included as standard. Before finger 

mounting the p/t plugs in the body tappings, pls. 

seal the

 

threads of the p/t plugs (DO NOT OVER 

TIGHTEN).

Inserting the insert:

For FlowCon AHU Wafer bodies size DN50-

DN80 (figure 1), a 3” stainless steel insert (either 

standard flow or high capacity) is available. It is 

recommended that the o-ring located around the 

insert is lubricated with silicone grease, before 

the insert is installed into the valve body.

IMPORTANT:

Never use mineral oil or petrol based grease or 

oil on the o-ring.

When inserting the insert, be assured to check 

the placement of the o-ring. There is no need to 

use tools - the insert can be inserted/removed 

by the fingers. Once the insert is installed in the 

valve body, the retainer clip is fitted to hold the 

insert in proper place.

Assembly drawing

FlowCon AHU Wafer

 

AHU Wafer housing 

 

O-ring 

 

3” Stainless steel insert (optional)

 

Retainer clip 

 

Extended p/t plug (2 pcs.).

Summary of Contents for AHU Wafer

Page 1: ...xtended pressure temperature fittings p t plugs are included as standard Before finger mounting the p t plugs in the body tappings pls seal the threads of the p t plugs DO NOT OVER TIGHTEN Inserting the insert For FlowCon AHU Wafer bodies size DN50 DN80 figure 1 a 3 stainless steel insert either standard flow or high capacity is available It is recommended that the o ring located around the insert...

Page 2: ...housing Flange not supplied by FlowCon Studs available upon request Nuts available upon request General Water must always be suitable treated clean and free of debris It is recommended that a strainer be installed prior to the valve body to prevent damage or blockage due to debris strainers are not supplied by FlowCon Warranty obligation Failure to abide by all recommendations as per this installa...

Page 3: ...F324480 3 41 12300 54 0 F3241135 3 47 12500 55 0 F3242110 F324855 3 53 12700 56 0 F3241140 3 58 12900 56 7 F324485 3 63 13100 57 5 F3242115 3 66 13200 58 0 F3241145 3 79 13600 60 0 F3241150 F3242120 F324490 F324860 3 94 14200 62 5 F3242125 4 00 14400 63 3 F324495 4 10 14800 65 0 F3242130 F324865 4 21 15100 66 7 F3244100 4 26 15300 67 5 F3242135 4 42 15900 70 0 F3242140 F3244105 F324870 Accuracy 5 ...

Page 4: ...LANCING VALVE WITH PRE SET INSERT FlowCon AHU Wafer 50 80mm 1W95000 04 2016 FlowCon International assumes no responsibility for mistakes if any in any printed material Denmark Dubai USA Singapore www flowcon com 4 ...