6
|
www.flowair.com
LEO XL2 | XL3 / BMS
LEO XL2 INOX / ST | XL3 INOX / ST
LEO XL2
LEO XL3
Gear | Fläkthastighet
III
II
I
III
II
I
Max airflow [m3/h ] | Max. luftflöde [m3/h
]
5800
4600
2900
5300
4100
2500
Power supply [V/Hz] | Kraftkälla [V/Hz]
230/50
Max current consumption [A] | Max. strömförbrukning [A]
2,3
1,8
1,4
2,4
1,8
1,4
Max power consumption [W] | Max. effektförbrukning [W]
520
370
270
550
370
270
IP/ Insulation class | IP Klass
54 /F
Max acoustic pressure level [dB(A)]* | Max. Ljudtryck [dB(A)]*
67,5
61,1
52,3
67,5
61,1
52,3
Horizontal range** [m] | Horisontell kastlängd** [м]
26,0
20,5
13,0
23,5
18,0
11,0
Vertical range*** [m] | Vertikal kastlängd*** [м]
8,5
7,0
4,7
7,7
6,2
4,1
Max heating water temperature [oC] | Max temperatur vatten [oC]
120 (INOX / ST: 130)
Max operating pressure [MPa] | Maximal drifttryck [MPa]
1,6
Connection | Anslutnings dimension
3/4”
Installation | Installation
Max working temperature [oC] | Maximal arbetstemperatur [oC]
60
Device mass [kg] | Vikt [kg]
23,2 (INOX: 29,9, ST: 29,9)
26,2 (INOX: 34,2, ST: 34,2)
Mass of device filled with water [kg] | Vikt med vatten [kg]
25,9 (INOX: 32,6, ST: 32,6)
30,3 (INOX: 38,3, ST: 38,3)
* Acoustic pressure level has been measured 5m from the unit in a 1500m3 space with a medium sound absorption coefficient | Ljudeffekt har
uppmätts
5m från
enheten i ett 1500m3 rum med medium ljud absorbtion coefficient.
** Horisontal isothermal range for 0,5 m/s border air stream speed | Horisontell isothermt avstånd på 0,5m
*** Vertical nonisothermal range for ΔT = 5
o
C and for 0,5 m/s border air stream speed |
Vertikalt icke-isometrisk inervall för ΔT = 5
o
C och med 0,5 m/s gräns för
luftströmshastigheten.
2. TECHNICAL DATA
2. T
eknisk Data
Indoor | Inomhus