background image

IMPORTANT

For best possible performance and continuous, satis-
factory operation, read these instructions before in-
stalling your new pump. 
Should service be required, this
manual can be a valuable guide, it should be kept near the
installation for ready reference.

INSTALLATION

LOCATION

Place unit as close to water source as possible to minimize
suction lift, obtain the best pumping performance, and aid in
priming. A typical portable installation is shown in Figure 1. 

For permanent installation, mount unit on a foundation that
will support the weight of pump and engine and also provide
stability while the pump is running. For most permanent
installations, it is advisable to bolt unit directly to foundation.

NOTICE: Settling and/or shifting during operation can cause
piping to place excessive strain on the pump and may dam-
age pump case. Set pump on hard level surface.

SUCTION CONNECTION

Connect either rigid pipe or flexible suction hose to pump
suction as shown in Figure 1. If hose is selected, hose must
be rated to hold the suction pressure and prevent collapse
while the pump is running. 

Make the suction line a continuous rise from the water
source to the pump. High spots can trap air and also make
priming difficult. Make sure all connections are tight and free
of air leaks.

NOTICE: Suction pipe or hose must be at least as large as the
pump suction inlet in order for the pump to operate properly.

Minimum depth for the suction inlet is determined by the
diameter of the suction line. See Figure 1.    

NOTICE:  This high pressure pump has a closed type im-
peller and will clog easily. Use a suction screen to keep
debris out of pump.

DISCHARGE CONNECTIONS

Your pump is equipped with a multiple port discharge to run
several lines at one time. Select the appropriate size for the
application. Pump output pressure will be reduced as addi-
tional lines are connected. For high pressure wash-downs or
firefighting, connect only one line. For irrigation applications
connect up to 3 small lines or one large line.

OPERATION

NOTICE:  Do not start or run pump dry or damage to the
mechanical seal will result.

NOTICE:  Add engine oil before startup. Refer to engine
owner/operator manual supplied with pump before startup.

PRIMING THE PUMP

A self priming pump only needs to be manually primed at the
first start-up. Once primed, under normal conditions the
pump will reprime automatically at each subsequent start-up.
If the pump is used in portable applications and the water has
been drained from the pump case, reprime before start-up

To prime, remove cap from top discharge outlet and fill pump
with water. Replace cap and start pump. The pump will

2

®

Discharge pipe diameter at
least one nominal pipe size
larger than discharge opening
in pump.

Use Concentric
Reducer to minimize
friction losses.

Strainer / Foot Valve

To keep debris from entering
pump suction and to maintain
pump prime after shut-off.

Provide rigid platform
for pump.

Example:
4" Pipe x 4 = 16" minimum depth.

Eccentric Reducer
flat side up.

Depth of suction inlet not less than
four (4) times the diameter of suction
pipe to eliminate vortexing.

Use pipe, tubing, or reinforced hose to make
suction connection. Hose must have suffi-
cient strength to resist collapse under the
pressure differential that occurs while pipe
is running.

Suction pipe size should be at least one
commercial pipe size larger than opening of
pump inlet. Flow velocity should not exceed
8 ft./sec.

Suction screen area must be at least four
times suction pipe area.

All suction piping must have a continuous
rise to the pump suction inlet. A 1/4 inch per
foot minimum slope is recommended.

Piping run and connection fittings should be
properly aligned and independently supported
to reduce strain on pump case.

Rigid wall flexible
suction hose with
quick connect shown.

Support pipe and
fittings as required.

1256 0994

Figure 1 – Typical Installation

Hazardous Suction.

Can trap persons
against suction inlet.

Always use strainer
on suction hose to
prevent entrapment.

Summary of Contents for FP5410

Page 1: ...ute question ou tout probl me concernant le fonctionnement de la pompe appeler le 1 800 365 6832 Pour toute question ou tout probl me concernant le fonctionnement du moteur s adresser au concessionnai...

Page 2: ...downs or firefighting connect only one line For irrigation applications connect up to 3 small lines or one large line OPERATION NOTICE Do not start or run pump dry or damage to the mechanical seal wi...

Page 3: ...stem for air leaks and or clack assembly F Pump takes too long to prime Check for air leaks or defective check valve G Flow through pump completely Locate and remove obstruction Attach strainer or par...

Page 4: ...bly 10 H05335 Pump Case 11 S24905 2 Capscrew pump case to seal plate 12 U178 920P Drain Plug 13 S24901 4 Capscrew pump case to seal plate short 14 S27123 6 Washer 15 S26456 6 Hex Nut 16 M10620 Dischar...

Page 5: ...nance or storage nor to other than normal application use or service including but not limited to operational failures caused by corrosion rust or other foreign materials in the system or operation a...

Page 6: ...ion de sortie de la pompe diminuera au fur et mesure que d autres conduites seront branch es sur la pompe Pour des nettoyages haute pression ou pour combattre les incendies ne branchez qu une seule ca...

Page 7: ...me recommand par le fabricant D Pi ces desserr es ou cass es Se reporter la Notice d utilisation du fabricant du moteur 2 POMPE E Ne s amorce pas R amorcer la pompe inspecter le syst me d aspiration l...

Page 8: ...anch it 12 U178 920P Bouchon de vidange 13 S24901 4 Vis chapeau corps de pompe sur plaque d tanch it courte 14 S27123 6 Rondelle 15 S26456 6 crou six pans 16 M10620 Bouchon de refoulement 1 1 2 pouce...

Page 9: ...nt y compris mais sans s y limiter aux produits ayant des pannes de fonctionnement caus es par la corrosion la rouille ou autre corps tranger dans le syst me ou des pro duits ayant fonctionn des press...

Page 10: ...nde OPERACION AVISO No arranque u opere la bomba en seco porque de hac erlo ocurrir n da os al sello mec nico AVISO A ada aceite al motor antes de arrancarlo Antes de arrancar la bomba consulte el man...

Page 11: ...e aire y o el cabezal de la bomba F La bomba toma mucho tiempo para cebar Compruebe si hay fugas de aire o si la v lvula de retenci n est defectuosa G El flujo a trav s de la bomba est total o parcial...

Page 12: ...905 2 Pernos capuchinos sellan la caja de la bomba a la placa de sellado 12 U178 920P Tap n de drenaje 13 S24901 4 Pernos capuchinos caja de bomba a placa de sellado cortos 14 S27123 6 Arandela 15 S26...

Page 13: ...naje incorrectos ni a nin guna otra cosa que no sea su aplicaci n uso o servicio normales incluyendo pero no limitado a fallas operacionales causadas por corrosi n oxidaci n u otros elementos extra os...

Page 14: ...14...

Page 15: ...15...

Page 16: ......

Reviews: