All Flomatic Electric Actuators are thoroughly tested and checked before shipment .  If 

installation will not occur immediately, actuator should be kept in a dry place.  Please 

DO NOT remove plugs from conduit entries until ready for wiring. 

             

2)  Operation

    

 

 

 

 

 

 

 

 

 

2.1)  Auto/Manual Operation 

 

 

 

 

 

 

 

 

 

      Auto/ Manual Shift operation as follows: 

1)

 

Manual Override:    

Caution: Before engaging manual override power must be

 

off.

   Push or Pull  the hand/auto declutching lever to engage clutch. (Handwheel 

may have to be “jockeyed” slightly.) After engaging clutch,  turn handwheel 

either to “Open” or “Closed”. 

2)

 

Auto Operation by Motor:  Once wiring is complete actuator is ready for 

operation and will  instantly  operate once electric power is energized.  If in 

manual mode when electric power is re-energized,  actuator will automatically 

declutch and operate. 

              2.2)  Valve Position Indication-    

                      Actuator Top mounted Visual position indication shows “OPEN” and  “CLOSED”       

                       valve position.                   

                   

              3)   Wiring Connections 

               3.1)   Top Housing Cover Removal                                                                                                                            

Remove the 4  Socket head  Housing Capscrews with a hex key wrench. Lift        

housing cover from actuator base.  Look for wiring diagram in plastic envelope. 

 

Caution!!  Read Before Operation!! 

When the actuator is operated for the 1

st

  time it is important to check the 

correct rotation of the motor. Otherwise serious damage may occur. 

1) Place Valve position at 45 degrees by turning the handwheel ,  energize  

the actuator to open or close  and check proper valve rotation direction. 

2) If Rotation direction is reverse, stop immediately and recheck wiring. 

FCEL Electric Actuator Operating Manual 

Summary of Contents for FCEL

Page 1: ... once electric power is energized If in manual mode when electric power is re energized actuator will automatically declutch and operate 2 2 Valve Position Indication Actuator Top mounted Visual position indication shows OPEN and CLOSED valve position 3 Wiring Connections 3 1 Top Housing Cover Removal Remove the 4 Socket head Housing Capscrews with a hex key wrench Lift housing cover from actuator...

Page 2: ...n screw 4 2 Setting the Open Limit Switch Upper Cam and Upper Switch 1 Pull the declutch lever and turn Handwheel counter clockwise to move the valve to the fully Opened position 2 Using a hex key wrench loosen the upper cam screw Opened LS 3 Adjust the cam to trip the upper cam switch LS then tighten screw 4 3 Mechanical Travel Limit Stops TLS 1 Closed Travel Limit Stop is on Left and Open Travel...

Page 3: ... removal 2 Machining The Drive bushing is machined to adapt to valve shaft or mounting coupler if actuator is not direct mounted to the valve If key keyway adaptation is used the directionof keyway should align with one of the drive busing screws 6 2 Reassembling the drive bushing 1 Check the relative position of valve and actuator Open Closed If not rotate the actuator to same position as valve 2...

Page 4: ...rol panel replace defective parts Control Panel 1st If NO Control Panel problem Check Actuator Then Actuator 3 Check the Actuator Motor and replace if necessary 4 Torq Switch Tripping turn main power off and follow Mechanical Trouble Shooting procedure 5 Check for faulty Limit switch with circuit check adjust or replace 6 All other electrical problems can be resolved by parts Replacement FCEL Actu...

Reviews: