Flo i-Controller Installation Manual Download Page 7

 

Installation Guide

 

IN-IC1-15

 

Title

:

 

Jace to i-Controller REV.200 MPU (575V 40–70 Ton) Conversion

 

 

Flō 

Tech Support 888-598-1198 

7

 

4-6DEC2021 

 

7.6

 

Wire Inputs  

Wire analog/digital inputs based on table 3. 

Existing 

Points 

i-Controller 

i-Controller 

Pin # 

 

NEW 

24 VAC Transformer Power 1 - 

1* 

 

24 VAC Transformer Power 1 + 

9* 

 

Space Temperature 1 SG 

 

Space Temperature 1 0V 

7* 

 

Space Humidity 1 SG 

 

Space Humidity 1 0V 

8* 

 

Space Humidity 1 Power 

16* 

 

Reuse 

Jenesys 

Sensor 

Supply Temperature SG 

 

Supply Temperature 0V 

7* 

 

NEW 

Reheat/Reclaim Inlet Probe 1 SG 

 

Reheat/Reclaim Inlet Probe 1 0V 

7* 

 

Reuse 

Jenesys 

Sensor 

Outside Air Temperature SG 

 

Outside Air Temperature 0V  

7* 

 

Return Temperature SG 

10 

 

Return Temperature 0V 

7* 

 

NEW 

Suction Press Comp 1 SG WHT 

11 

 

Suction Press Comp 1 0V BLK 

8* 

 

Suction Press Comp 1 Pwr RED 

15* 

 

Discharge Press Comp 1 SG WHT 

12 

 

Discharge Press Comp 1 0V BLK 

8* 

 

Discharge Press Comp 1 Pwr RED 

15* 

 

Suction Press Comp 2 SG WHT 

13 

 

Suction Press Comp 2 0V BLK 

8* 

 

Suction Press Comp 2 Pwr RED 

15* 

 

Discharge Press Comp 2 SG WHT 

14 

 

Discharge Press Comp 2 0V BLK 

8* 

 

Discharge Press Comp 2 Pwr RED 

15* 

 

 
 
 
 
 
 
 
 
 

Existing 

Points 

i-Controller 

i-Controller Pin 

 

See Wiring 

Diagram  

Smoke Detector/ 

Emergency Shutdown SG 

40 

 

Smoke Detector/ 

Emergency Shutdown 0V 

61* 

 

Airflow Switch SG 

41 

 

Airflow Switch 0V 

61* 

 

Clogged Filter SG 

42 

 

Clogged Filter 0V 

61* 

 

Load Shed SG (if 

equipped) 

45 

 

Load Shed 0V (if 

equipped) 

61* 

 

NEW 

Drain Pan Float Switch SG 

43 

 

Drain Pan Float Switch 0V 

61* 

 

Phase Monitor SG 

44 

 

Phase Monitor 0V 

61* 

 

 
 

Existing 

Points 

Expansion Module A 

Expansion 

A Pin # 

 

NEW 

24 VAC Transformer Power 2 - 

1* 

 

24 VAC Transformer Power 2 + 

9* 

 

CO2 SG (if equipped) 

 

CO2 0V (if equipped) 

15* 

 

CO2 +24 (if equipped) 

CSTB1  

 

Red** 

 

CO2 -24 (if equipped) 

CSTB1 

Black** 

 

See 

Wiring 

Diagram  

Outdoor Humidity SG  

 

(if equipped) 

 

Outdoor Humidity 0V  

15* 

 

(if equipped) 

 

Outdoor Humidity Power  

 

(if equipped) 

 

 
 

 

Summary of Contents for i-Controller

Page 1: ...oat Switch 4 6 5 Install New CO2 Sensor 5 6 6 Install Space Temp RH Combo Sensor 5 7 Install The i Controller Components 6 7 1 Remove Existing Jenesys Controls 6 7 2 Install New i Controller and Expan...

Page 2: ...rols Screwdriver Step Drill Bit for CO2 Sensor Probe Installation Refrigerant Tee with Schrader Depressor 2 Schrader Cores 4 Conductor Shielded Twisted Wire or Equivalent 5 Conductor Shielded Twisted...

Page 3: ...gths of Black 18 AWG wire to the following i Controller green plug connection points 1 7 8 25 28 61 See Figure 1 for plug orientation Attach 10 lengths of Red 18 AWG wire to the following i Controller...

Page 4: ...the 0 667 PSI Discharge transducers on the liquid lines of circuits 1 2 3 4 If there are spare service ports on the unit install the transducers on a spare service port If spare service ports are not...

Page 5: ...w Figure 3 CO2 sensor location inside the unit Wire the new CO2 based on the following see Figure 4 24VAC Red wire 24VAC Black wire COM Green wire CO2 SIGNAL White wire NOTE Do not wire the CO2 sensor...

Page 6: ...1 down 2 up 3 down 4 down NOTE The actual switch may be white but for illustrative purposes the switch is black in the Figure 6 below Figure 6 Fl i Controller Expansion Addressing Wire the 2 expansion...

Page 7: ...Comp 1 SG WHT 12 Discharge Press Comp 1 0V BLK 8 Discharge Press Comp 1 Pwr RED 15 Suction Press Comp 2 SG WHT 13 Suction Press Comp 2 0V BLK 8 Suction Press Comp 2 Pwr RED 15 Discharge Press Comp 2...

Page 8: ...Reheat Reclaim Inlet Probe 2 SG 29 Reheat Reclaim Inlet Probe 2 0V 28 This indicates that you will be attaching to a 10 wire not a pin This indicates that you will be attaching to the CSTB1 Table 3 In...

Page 9: ...aim do not wire 24VAC to point 86 The dry common from the refrigeration rack reclaim control is connected to point 86 Existing Points Expansion Module A Expansion A Pin See Wiring Diagram in Unit ERV...

Page 10: ...With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the and set the value Press ENTER a second time to accept changes The controller will au...

Page 11: ...hen press ENTER Dehumidification mode is now turned OFF 9 6 Heating Test Mode From the Field Technician Options screen press T2 Test Modes Press T3 2 Operational Tests Use to navigate to the Heat Test...

Page 12: ...ions button Using the to navigate to the value that you wish to change With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the set the value...

Page 13: ...l Tech Support 888 598 1198 13 4 6DEC2021 11 Appendix 11 1 i Controller Layout 1 24VAC Power Point 9 and 1 2 Analog Inputs 3 Digital Inputs 4 Digital Outputs 5 Analog Outputs 11 2 Expansion Board Layo...

Reviews: