Flo i-Controller REV.200 Troubleshooting Manual Download Page 7

 

Troubleshooting Guide 

 

CN-IC1-09

 

Title

:

 

i-Controller REV.200 Alarms (Troubleshooting)

 

 

EXTERNAL

  

1-19MAY2021 

 

Fan Fail Alarm 

 
The fan fail alarm is generated when a fan fails to start for more than 10-minutes when enabled by the controller. When a 
fan fail alarm is generated, 

ALARM

” will be displayed next to “

Fan Status

” on the 

Alarms

 screen.   

 
This alarm is generated when the digital airflow switch, located in the fan cabinet, detects a loss of airflow and switches 
from normally open to closed. The Fan Fail alarm may also be generated during a Phase Loss alarm.   
 
When a fan fail alarm occurs, the Fl

ō

 unit will be shut down. The fan fail alarm must be manually reset using the i-Controller 

Visograph display. 
 

Wait 10 minutes

If the airflow switch does not close 

within 10 minutes, the unit will re-alarm

Did the fan 

start?

Yes

No

Did the alarm 

reappear?

No

Contact Tech 

Support

1-888-598-1198

• 

Check the Digital Phase Monitor for alarms (see page 12)

• 

Verify switch operation

• 

Verify the alarm input points on the board or controller

• 

Check switch wiring and connections

• 

Check that VFD is in remote mode (RE), not local mode (LO)

• 

Check VFD for alarms

• 

Check if VFD is in Base Block mode (displayed as 

 

bb

  

• 

Verify that controller is calling for the fan to turn on

• 

Verify that motor has power applied

• 

For power in, check main power

• 

For power out, check motor leads

• 

Check the fan fail circuitry

• 

Verify the motor by checking the windings

Issue resolved

Yes

Is the issue 

resolved?

No

Yes

Fan Fail Alarm is present

Reset the alarm 

(see instructions below)

 

Summary of Contents for i-Controller REV.200

Page 1: ...High Discharge Trip Alarm 4 Compressor Proof Alarm 5 Drain Pan Overflow Alarm 6 Fan Fail Alarm 7 Heat Alarm 8 Heat Reclaim Notice if equipped 9 High Discharge Pressure Alarm 10 High Suction Pressure A...

Page 2: ...the filter bank and cooling coil The sensor s range of adjustment is 0 17 to 5 0 in W C with contact closure on rise The switch is mounted in the fan compartment with terminal connections in the low v...

Page 3: ...additional maximum specified percentage set to 15 by default Once the CO2 level in the space is lowered the unit will resume regular operation CO2 level higher than set point Verify unit operation se...

Page 4: ...scharge Trip Compressor Proof Failure Check compressor and condenser operation Check therefrigerant level for overcharge Check condenser coil for cleanliness Check for airflow issues including dirty f...

Page 5: ...etected No Comp Proof will be displayed next to COMP on the Alarms screen When a successful proof signal is received by the controller the compressor proof alarm will automatically reset Compressor Pr...

Page 6: ...hen the water level in the drain pan decreases and the float switch input closes the drain pan overflow alarm will automatically reset Drain Pan Float Switch Alarm present Drain pan overflowing Verify...

Page 7: ...et using the i Controller Visograph display Wait 10 minutes Iftheairflow switch does not close within 10 minutes the unit will re alarm Did the fan start Yes No Did the alarm reappear No Contact Tech...

Page 8: ...pressureis within the allowable range Natural Gas 6 10 5inch WC Propane 10 13 inch WC Check that the controller is calling for heat Check for safeties and interlocks Check wiring and connections Check...

Page 9: ...heat reclaim has been disabled the heat reclaim notice will automatically reset Heat Reclaim Notice Present Reclaim Active Verify compressors operation Verify unit is equipped with heat reclaim Verify...

Page 10: ...t least 5 minutes the high discharge pressure alarm will be automatically reset Alarm cleared Yes Contact Tech Support 1 888 598 1198 No Issueresolved Check compressor and condenser operation Check th...

Page 11: ...ction pressure falls below the 130psi during dehumidification or 160psi during cooling the high suction alarm will automatically reset Has thealarm cleared Yes Contact Tech Support 1 888 598 1198 No I...

Page 12: ...een When suction pressure increases above 100psi the low suction pressure alarm will automatically reset Low Suction Pressure Alarm present Yes No Alarm cleared Yes Contact Tech Support 1 888 598 1198...

Page 13: ...rsed Upon detection of one or more of these conditions the monitor opens the secondary 24VAC circuit disabling the control circuit of the Fl Unit A phase loss alarm may generate a fan fail alarm Addit...

Page 14: ...ed Notice will be displayed next to Ref Lk Status on the Alarms screen When the refrigerant leak is no longer signaled by the refrigeration system and the digital input is opened the i Controller and...

Page 15: ...iled navigate to the alarms menu and select sensor status When the failed sensor condition has been corrected the sensor failure alarm will automatically reset Sensor Failure Alarm present Check that...

Page 16: ...or circuit and will trigger an emergency shutdown of the unit When the smoke detector circuit is closed the alarm will automatically reset Smoke Detector Alarm is present Smoke detector connections cl...

Page 17: ...e that the OFF value is highlighted 2 Press the T5 button and the value should blink 3 Using the and buttons increase and decrease the value until ON appears 4 Once the desired value has been reached...

Reviews: