Troubleshooting Guide
CN-IC1-09
Title
:
i-Controller REV.200 Alarms (Troubleshooting)
EXTERNAL
4
1-19MAY2021
Compressor High Discharge Trip Alarm
The high discharge trip is generated when a high discharge pressure condition is present and compressor proof fails. When
a high discharge trip alarm is generated,
“
ALARM
” will be displayed next to “
COMP High Dis Trip
” on the
Alarms
screen.
When the discharge pressure decreases, and the compressor proof is made, the compressor high discharge trip will
automatically reset.
Compressor High
Discharge Trip
Compressor
Proof Failure
•
Check compressor and
condenser operation
•
Check the refrigerant level for
overcharge
•
Check condenser coil for
cleanliness
•
Check for airflow issues
(including dirty filter, dirty or
clogged evaporator coil etc.)
•
Check for non-condensables in
refrigerant
•
High ambient conditions may be
responsible for the high
discharge pressure
Yes
No
•
Check the suction pressure
transducer
s voltage output
against that of spec sheet
•
Verify the alarm input points
on the board or controller
•
Verify that program is set for
the correct scale and type of
sensor
•
Check wiring and connections
Alarm cleared?
Contact Tech
Support
1-888-598-1198
No
Issue resolved
Check refrigerant
pressure (Validate
controller reading)
Yes