Troubleshooting Guide
CN-IC1-09
Title
:
i-Controller REV.200 Alarms (Troubleshooting)
EXTERNAL
16
1-19MAY2021
Smoke Detector Alarm
This smoke detector alarm is generated when smoke is detected in the unit or air stream. When the smoke detector alarm
is generated, “
ALARM
” will be displayed next to “
Smoke Det. Status
” on the
Alarms
screen.
This alarm is generated via the opening of the normal closed smoke detector circuit and will trigger an emergency shutdown
of the unit.
When the smoke detector circuit is closed, the alarm will automatically reset.
Smoke Detector
Alarm is present
Smoke
detector connections
closed?
Yes
•
Reset the smoke detector
•
Check field wiring and
connections
No
•
Check unit wiring and
connections
•
Verify the alarm input
points on the board or
controller
Alarm cleared?
Yes
Contact Tech
Support
1-888-598-1198
No
Smoke detector
installed on LVTB?
Install smoke detector (a
temporary jumper may be
installed for testing, but must be
removed afterwards)
No
Yes
Is the issue
resolved?
No
Issue resolved
Yes