Flo i-Controller REV.200 Troubleshooting Manual Download Page 11

 

Troubleshooting Guide 

 

CN-IC1-09

 

Title

:

 

i-Controller REV.200 Alarms (Troubleshooting)

 

 

EXTERNAL

  

11 

1-19MAY2021 

 

High Suction Pressure Alarm 

 
For a digital compressor, the high suction pressure alarm is generated when the suction pressure increases above 140psi 
for 10-minutes when a compressor is enabled during dehumidification or 170psi in cooling mode. For a fixed compressor 
the high suction pressure alarm is generated with the suction pressure increases above 160psi and reset when the pressure 
decreases below 150psi. When a high suction pressure alarm is generated, 

ALARM

” will be displayed next to “

High Suct 

Press

” on the 

Alarms

 screen. 

 
When  dehumidification  and  cool  mode  are  disabled,  or  if  the  suction  pressure  falls  below  the  130psi  during 
dehumidification or 160psi during cooling, the high suction alarm will automatically reset. 
 

Has the alarm 

cleared?

Yes

Contact Tech 

Support

1-888-598-1198

No

Issue resolved

• 

Check compressor and condenser 
operation

• 

Check the refrigerant level for 
overcharge

• 

Check condenser coil for 
cleanliness

• 

Check for airflow issues (including 
dirty filter, dirty or clogged 
evaporator coil etc.)

• 

Check for non-condensables in 
refrigerant

• 

High ambient conditions may be 
responsible for the high discharge 
pressure

• 

Check the suction pressure 
transducer

 

s voltage output 

against that of spec sheet

• 

Verify the alarm input points on 
the board or controller

• 

Verify that program is set for the 
correct scale and type of sensor

• 

Check wiring and connections

High Suction 

Pressure Alarm 

present

Pressure above 

the set point?

Yes

No

Check refrigerant pressure 

(Validate controller reading)

 

Summary of Contents for i-Controller REV.200

Page 1: ...High Discharge Trip Alarm 4 Compressor Proof Alarm 5 Drain Pan Overflow Alarm 6 Fan Fail Alarm 7 Heat Alarm 8 Heat Reclaim Notice if equipped 9 High Discharge Pressure Alarm 10 High Suction Pressure A...

Page 2: ...the filter bank and cooling coil The sensor s range of adjustment is 0 17 to 5 0 in W C with contact closure on rise The switch is mounted in the fan compartment with terminal connections in the low v...

Page 3: ...additional maximum specified percentage set to 15 by default Once the CO2 level in the space is lowered the unit will resume regular operation CO2 level higher than set point Verify unit operation se...

Page 4: ...scharge Trip Compressor Proof Failure Check compressor and condenser operation Check therefrigerant level for overcharge Check condenser coil for cleanliness Check for airflow issues including dirty f...

Page 5: ...etected No Comp Proof will be displayed next to COMP on the Alarms screen When a successful proof signal is received by the controller the compressor proof alarm will automatically reset Compressor Pr...

Page 6: ...hen the water level in the drain pan decreases and the float switch input closes the drain pan overflow alarm will automatically reset Drain Pan Float Switch Alarm present Drain pan overflowing Verify...

Page 7: ...et using the i Controller Visograph display Wait 10 minutes Iftheairflow switch does not close within 10 minutes the unit will re alarm Did the fan start Yes No Did the alarm reappear No Contact Tech...

Page 8: ...pressureis within the allowable range Natural Gas 6 10 5inch WC Propane 10 13 inch WC Check that the controller is calling for heat Check for safeties and interlocks Check wiring and connections Check...

Page 9: ...heat reclaim has been disabled the heat reclaim notice will automatically reset Heat Reclaim Notice Present Reclaim Active Verify compressors operation Verify unit is equipped with heat reclaim Verify...

Page 10: ...t least 5 minutes the high discharge pressure alarm will be automatically reset Alarm cleared Yes Contact Tech Support 1 888 598 1198 No Issueresolved Check compressor and condenser operation Check th...

Page 11: ...ction pressure falls below the 130psi during dehumidification or 160psi during cooling the high suction alarm will automatically reset Has thealarm cleared Yes Contact Tech Support 1 888 598 1198 No I...

Page 12: ...een When suction pressure increases above 100psi the low suction pressure alarm will automatically reset Low Suction Pressure Alarm present Yes No Alarm cleared Yes Contact Tech Support 1 888 598 1198...

Page 13: ...rsed Upon detection of one or more of these conditions the monitor opens the secondary 24VAC circuit disabling the control circuit of the Fl Unit A phase loss alarm may generate a fan fail alarm Addit...

Page 14: ...ed Notice will be displayed next to Ref Lk Status on the Alarms screen When the refrigerant leak is no longer signaled by the refrigeration system and the digital input is opened the i Controller and...

Page 15: ...iled navigate to the alarms menu and select sensor status When the failed sensor condition has been corrected the sensor failure alarm will automatically reset Sensor Failure Alarm present Check that...

Page 16: ...or circuit and will trigger an emergency shutdown of the unit When the smoke detector circuit is closed the alarm will automatically reset Smoke Detector Alarm is present Smoke detector connections cl...

Page 17: ...e that the OFF value is highlighted 2 Press the T5 button and the value should blink 3 Using the and buttons increase and decrease the value until ON appears 4 Once the desired value has been reached...

Reviews: