background image

       IOM-MPF155 2018

 

Page 1

 

 

 

 
 
 
 
 

 

Flo-Tite Bottom Entry Series

 

Models MPF155

 

Flanged End Ball Valves

 

Installation, Operation and Maintenance Manual

 

Note: Before using a valve, read the entire IOM carefully and make sure you have a clear understanding  of all 
information  included.

 

 

This manual describes the procedures for the safe and efficient installation, operation and maintenance  of

 

Flo-Tite Flanged Series Ball Valves. 

Failure to follow the procedures in this manual may result in Flo-Tite 

warranties being voided. 

Problems with the operation and maintenance  of these valves should be directed 

to the nearest Flo-Tite Representative.

 

 

The Flo-Tite Flanged Series are designed as one piece body.  This line of valves utilizes the “free floating” ball 
principle.  The ball is not fixed, but is free to move with the line pressure.  As a result, these valves are capable 
of tight shut-off with the flow in either direction or dead-ended, regardless of the position of the valve in the 
line.  The downstream seat, which is opposite the pressurized side, of a closed valve must carry the load 
exerted by the line pressure on the ball, while the upstream seat is subject to little load or wear.  For this 
reason, it is sometimes possible to increase useful seat life by turning  the valve end-for-end  in the pipeline.

 

 

 

INSTALLATION:

 

 

A. Receiving and Preparation  Procedure

 

 

 

A1. Remove shipping protection

 

A2. Inspect the valve(s) for transportation  damage* 
A3. Inspect the valve bore and remove any debris

 

A4. Cycle the valve and inspect the valve for smooth operation, size permitting

 

A5. As shipped from the factory, valves may contain a silicone based lubricant.  This is for break-in and may 
be removed if it is objectionable for a particular application by disassembling and solvent washing.

 

 

*If transportation  damage is found, immediately take pictures for record purposes and contact the inbound 
carrier to submit a claim.

 

 

B. Installation Procedure

 

 

 

B1. General – The valve may be fitted in any position in the pipeline.  Prior to installing the valve, the pipe on 
either side of the intended  installation should be checked to be free of dirt, debris, weld slag, etc. to prevent 
damage to the seats, seals and surface of the ball.  The piping must also be free of tension or compression.

 

 

WARNING 

– Never use the valve as a pipe support or structural member.