4
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should
have received the following items inside of package:
The unit x 1
User manual x 1
Communication cable x 2
Software CD x 1
Mounting plate x 1
Screws x 4
Installation
Wall mounted
Consider the following points before selecting where to install:
Do not mount the inverter on flammable construction materials.
Mount on a solid surface
Install this inverter at eye level in order to allow the LCD display to be read at all times.
The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
The recommended installation position is to be adhered to the wall vertically.
For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50
cm above and below the unit.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Please follow the steps as below to finish the installation.
Employ the mounting plate as a template for marking
the positions of the boreholes. Mount the mounting plate
with supplied screws to fix the plate in place.
Insert two screws to the two sides of inverter as showed
in the figure. Please don’t screw them tightly at this
time. Then, place the inverter onto the mounting plate
and fix two screws tightly.
Then, insert the other two screws on the two sides of
inverter as showed in the figure and fix them tightly.
For proper air circulation to dissipate heat, please keep
the space around the inverter more than 20 cm.