The heaters can be switched ON/OFF manually using a suitable double pole switch to provide localised heating.
However for optimum temperature control we recommend using a suitable room thermostat. For advice please
contact your distributor.
DESCRIPTION & SPECIFICATION
CR radiant heaters are designed to provide primary, localised or perimeter heating in residential, commercial and
industrial buildings. For optimum performance the heaters should be installed between 2.4m and 3.5m above floor
level either by direct ceiling mounting using the optional bracket (CRB), laid into a standard 24mm “T” section
suspended ceiling grid or suspended from the ceiling using suitable chains or wires.
Model
3CR
6CR
Power
300W
600W
Voltage
230V~
230V~
Current
1.3A
2.6A
Dimensions (L x W x H)
595 x 595 x 25mm
1195 x 595 x 25mm
Weight
6.2kg
11.9kg
Minimum installation height
1.8m
1.8m
Recommended installation height
2.4 - 3.5m
2.4 - 3.5m
IP rating
IP 55
IP 55
IMPORTANT:
READ CAREFULLY BEFORE USE AND KEEP FOR FUTURE REFERENCE.
Ÿ
Do not install the heater directly below electrical outlets when using the optional ceiling mounting bracket.
Ÿ
CAUTION — Some parts of this product can become very hot and cause burns. Particular attention has
to be given where children and vulnerable people are present.
Ÿ
Check the heater for damage before installation. If the supply cord is damaged, it must be replaced by the
manufacturer or it’s service agent.
Ÿ
This heater must not be used in ambient temperatures exceeding 30°C.
Ÿ
This heater is a Class I appliance and to comply with the Wiring Regulations it must be earthed.
Ÿ
The surface of the panel can be cleaned using a soft cloth and a mild aqueous mild detergent. The heater must
be switched off, allowed to cool and isolated from the electrical supply before cleaning.
Ÿ
The heater must be installed by a qualified electrician in accordance with current wiring regulations. The
heating must be connected to the fixed wiring and protected by 30mA residual current device (RCD) and a
suitable fuse or circuit breaker.
Ÿ
Do not use in hazardous areas.
Ÿ
The heater must be connected to a circuit with means for disconnection from the supply having contact
separation of at least 3mm in all poles.
Ÿ
The ceiling surface must be capable of supporting the weight of the heater. If in doubt please check.
Ÿ
The heater must not be installed at a height less than 1.8m from the floor.
SAFETY INSTRUCTIONS
Ÿ
WARNING
: This heater is not equipped with a device to control the room temperature. Do not use this heater in
small rooms when they are occupied by persons not capable of leaving the room on their own, unless constant
supervision is provided.
Ÿ
Children of less than 3 years should be kept away unless continuously supervised. Children aged from 3 years
and less than 8 years shall only switch on/off the appliance provided that it has been placed or installed in its
intended normal operating position and they have been given supervision or instruction concerning use of the
appliance in a safe way and understand the hazards involved. Children aged from 3 years and less than 8
years shall not plug in, regulate and clean the appliance or perform user maintenance.
CR Radiant Ceiling Panel Heaters
Installation and User Instructions
FLEXEL