VESDA-E VEU-A10 Product Guide
www.xtralis.com
41
4.3.7
Unmonitored General Purpose Input (GPI)
The Unmonitored GPI is a programmable input which can be configured to initiate a number of different
actions, including, by default, a Remote Reset function. Refer to Section 5.5.9 on page 69 for further
information.
A voltage input of between 5V and 30V signals GPI ON. Less than 2V signals GPI OFF. The input is isolated
from the system by an opto-coupler device.
4.3.8
Monitored General Purpose Input (GPI) Wiring
The monitored GPI senses contact closure and is configurable to initiate the same actions as the unmonitored
GPI. "Remote Reset" is the default setting. A closed contact signals GPI ON and open contact signals GPI
OFF.
A 10K end of line resistor is used to allow the detector to monitor for open circuit faults in the wiring from the
detector to the contact. Refer to Section 4.3.11 for information on correct wiring of the End of Line resistor.
Summary of Contents for VESDA-E VEU-A10
Page 1: ...VESDA E VEU A10 Product Guide November 2018 Document 22077_12 Part Number 30334 ...
Page 2: ......
Page 10: ...VESDA E VEU A10 Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 22: ...VESDA E VEU A10 Product Guide 16 www xtralis com This page is intentionally left blank ...
Page 54: ...VESDA E VEU A10 Product Guide 48 www xtralis com This page is intentionally left blank ...
Page 82: ...VESDA E VEU A10 Product Guide 76 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEU A10 Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 110: ...VESDA E VEU A10 Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 116: ...VESDA E VEU A10 Product Guide 110 www xtralis com Z zone 59 61 79 105 ...