intermediate heat exchanger must be installed upstream of the heat exchangers on the
chiller assembly.
8.5.2 Correction factors
Ethylene glycol solutions
Water and ethylene glycol solutions used as a heat carrier in the place of water reduce
the performance of the unit. Multiply the performance figures by the values given in the
following table.
Freezing point
0
-5
-10
-15
-20
-25
Percentage of ethylene glycol by weight
0
12%
20%
28%
35%
40%
Flow-rate correction factor
cQ
1
1,02
1,04
1,075
1,11
1,14
Pressure drop correction factor
cdp
1
1,07
1,11
1,18
1,22
1,24