Medium Connections
Multi
-DENCO
56
FläktGroup DC-2013-0101-GB • Subject to modifications • R4-05/2018
6.2.5 Thermal expansion
All pipework, which is subject to changes in temperature, expands and contracts. The
routing and joining of the pipework must be capable of absorbing this movement. An
example of the rate of expansion on a
Multi
-DENCO unit is as follows:
Pipework with multiple bends and where any straight lengths are short prevents issues
with expansion. If long, straight pipework is unavoidable, the following methods can be
used:
– Expansion loops
– Offsets
– Anacondas (see manufacturer's datasheets for details)
If using expansion loops or offsets, the following minimum dimensions must be obser-
ved:
Fig. 6-3
Pipe
Pipe Operating
Temperature
°C
Expansion in 0 °C
Temperature
mm/m
Expansion in 21 °C
Temperature
mm/m
Hot Gas Line
80
1.35
1.00
Liquid Line
45
0.76
0.41
Suction Line
12
0.20
0.15
Tab. 6-3
Expansion Loops
Offset
Tube Outer
Diameter
Size of expansion movement [mm]:
10
20
30
50
70
100
Length (L) of required loop or offset [mm]:
1/2" or 12 mm
200
275
350
425
500
550
5/8" or 16 mm
200
300
375
450
550
650
3/4" or 18 mm
225
325
400
500
600
700
7/8" or 22 mm
225
350
425
550
650
750
1 1/8" or 28 mm
250
375
450
600
700
850
1 3/8" or 35 mm
250
400
475
650
800
900
1 5/8" or 42 mm
275
425
500
700
850
1000
Tab. 6-4
Summary of Contents for Multi-DENCO
Page 1: ...Multi DENCO OPERATION MANUAL ...
Page 117: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 117 ...
Page 118: ...Multi DENCO 118 FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 ...
Page 119: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 119 ...