
Technical Description
Multi
-DENCO
28
FläktGroup DC-2013-0101-GB • Subject to modifications • R4-05/2018
3.2
Operating limits
3.3
Operating modes
A basic
Multi
-DENCO unit only has the capacity to perform cooling, therefore only
being able to control the upper limit of the temperature of the room. Heaters and humi-
difiers can be added to the design to allow for control of both the lower limit of tempe-
rature and to control the humidification of the room.
Cooling
The main function of a close control unit is to cool the air within a room to a defined set
point.
If using refrigerant (A-Version & X-Version), this is achieved by adjusting compressor
speed, expansion valve opening and indoor and outdoor fan speed.
If using chilled water (C-Version), this is accomplished by adjusting the water valve
opening and adjusting the indoor fan speed.
Both methods use variable technology to match the heat of rejection by the
Multi
-DENCO unit to the volume of heat produced within the room.
Multi
-DENCO
Unit
A-Version
C-Version
X-Version
CombiCool Circuit
Indoor Temperature Minimum
°C
10
10
10
10
Indoor Temperature Maximum
°C
40
40
32
40
Indoor Humidity (Absolute) Minimum
g/kg
2
2
2
2
Indoor Humidity (Absolute) Maximum
g/kg
18
18
18
18
Outdoor Ambient Air Temperature Minimum (Standard)
°C
-20
N/A
-15
N/A
Outdoor Ambient Air Temperature Minimum (with low ambient kit)
°C
-40
N/A
N/A
N/A
Outdoor Ambient Air Temperature Maximum
°C
55
N/A
46
N/A
Condensing Temperature Minimum
°C
35
N/A
35
N/A
Condensing Temperature Maximum
°C
64
N/A
64
N/A
Maximum Operating Pressure (High)
MPa
4.32
0.6
2
4.15
0.6
2
Maximum Operating Pressure (Low)
MPa
4.32/3.00
1
N/A
4.15
N/A
1
4.32 MPa for unit sizes 010 to 065. 3.00 MPa for unit sizes 092 & 130
2
Default configuration for standard design. 1.00 MPa for certain configurations
DENCO-OfficeCool
Unit
H-Version
O-Version
Indoor Temperature Minimum
°C
10
10
Indoor Temperature Maximum
°C
32
40
Indoor Humidity (Absolute) Minimum
g/kg
2
2
Indoor Humidity (Absolute) Maximum
g/kg
18
18
Outdoor Ambient Air Temperature Minimum
°C
-15
N/A
Outdoor Ambient Air Temperature Maximum
°C
46
N/A
Condensing Temperature Minimum
°C
35
N/A
Condensing Temperature Maximum
°C
64
N/A
Maximum Operating Pressure (High)
MPa
4.15
0.6
1
Maximum Operating Pressure (Low)
MPa
4.15
N/A
1
Default configuration for standard design. 1.00MPa for certain configurations
Summary of Contents for Multi-DENCO
Page 1: ...Multi DENCO OPERATION MANUAL ...
Page 117: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 117 ...
Page 118: ...Multi DENCO 118 FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 ...
Page 119: ...Multi DENCO FläktGroup DC 2013 0101 GB Subject to modifications R4 05 2018 119 ...