flakt woods Roofmaster STEF Series Installation And Maintenance Instructions Spare Parts Download Page 4

4

Version 22.02.2002 © Fläkt W

oods Oy

Roofmaster STEF and STOF

Fig. 3

Fig. 4

Electrical wiring

(To be carried out by an authorised electrician.) The
wiring diagrams are on page 5 The wiring diagrams for
the speed controllers (STYR), are included in the supply.
A. Power roof ventilator with SAFE safety isolating

switch, Figure 3.

If the STEF power roof ventilator has been equipped
with a factory-fitted SAFE safety isolating switch, the
electrical wiring between the motor and safety isolating
switch has already been done at the factory. The safety
isolating switch has been mounted in a recess in the
side of the ventilator casing. Only the front section of the
switch is exposed.
1. Open the safety isolating switch protective cover.
2. Open safety isolating switch cover.
3. Run the flexible power supply cable through the

cable seal at the lower edge of the ventilator casing
to the safety isolating switch. Adjust the length
of the electric cable so that sufficient slack will be
available for raising the fan for servicing.

4. Wire the connections, close the safety isolating

switch and the cover.

5. Check to make sure that the switch functions

correctly.

NB. In case of spark-proof version, the safety
isolation switch shall not be mounted in the fan
casing. If the spark-proof roof ran is ordered with
safety isolation switch, it is mounted externally
on the fan casing.

B. Power roof ventilator with a safety isolating switch,

which is to be fitted at the building site.

If the power roof ventilator has not been equipped with a
factory-fitted safety isolating switch, fig. 4, the safety
isolating switch can be mounted at an optional location,
for example in the side of the roof duct or in the side of
the power roof ventilator.
1. Mount the safety isolating switch at the desired

location.

2. Wire the connections inside the safety isolating

switch.

3. Open the connection cover on the side of the power

roof ventilator. To facilitate the electric connection
open the roof of the power roof ventilator and pull up
the insulated cover plates of the motor.

4. Open the junction box on the electric motor.
5. Run the flexible power supply cable through the

cable seal at the lower edge of the ventilator casing
to the connection opening and then to the motor.
Adjust the length of the electric cable so that sufficient
slack will be available for raising the fan for servicing.

6. Make the electrical connections to the motor.
7. Mount the panels and the top grille.
8. Close the junction box in the switch and make sure

that the safety isolating switch functions correctly.

Electrical wiring

Cable gland

Cable gland

Summary of Contents for Roofmaster STEF Series

Page 1: ...Roofmaster STEF and STOF Installation and Maintenance Instructions Spare parts ...

Page 2: ...EF and STOF Contents Mounting 3 Electrical wiring 4 Wiring diagram 5 Wiring diagram 6 Servicing 7 Spare parts 8 Spare parts 9 CE 10 NB The power roof fan must be isolated from the mains power supply appr 2 minutes before starting any maintenance work ...

Page 3: ... its base plate to the roof duct flanges tapped holes using the four M8 x 35 screws supplied in the bag of accessories To mount the STEF on an in situ built chimney with the MORA STEZ 03 mounting frame If the chimney has exactly the same dimensions as those of the BOGA roof duct no mounting frame will be required i e the ventilator can be mounted as described in the preceding instruction 1 Fit the...

Page 4: ...olation switch shall not be mounted in the fan casing If the spark proof roof ran is ordered with safety isolation switch it is mounted externally on the fan casing B Power roof ventilator with a safety isolating switch which is to be fitted at the building site If the power roof ventilator has not been equipped with a factory fitted safety isolating switch fig 4 the safety isolating switch can be...

Page 5: ...YR 36 Safety isolation switch SAFE Electrical junction box not included in the supply Safety isolation switch SAFE Electrical junction box not included in the supply Single phase motor with transformer STYR 36 STEF STOF 3 4 Single phase motor with transformer STYR 36 STEF STOF 1 2 This connection prevents the automatic restart when the thermocontact has switched off the motor Single phase motor ST...

Page 6: ...or star coupled Three phase two speed motor with separate windings Spark proof version STEF 7 006 c 9 coupled 400 V Wiring diagram Safety isolation switch SAFE Electrical junction box not included in the supply Safety isolation switch SAFE Electrical junction box not included in the supply ...

Page 7: ...ng of the ventilator base plate and mounting frame are in good condition 5 Clean as required The sound insulated fan casing surfaces can also be cleaned since the insulation is protected by perforated sheet metal 6 On having completed the servicing work release the stay support by depressing the locking lever see Figure 5 and lower the fan section back to its initial position Re tighten the arrest...

Page 8: ...mm IEC Spare parts code Motor Reservdelskod Motor Varaosakoodi Moottori Varuosa kood Mootor Ersatzteilkode Motor Reservedelskode Motor Spare parts STEF STOF 1 104 c 1 3 STEF STOF 1 004 c 1 3 STEF STOF 1 406 c 1 3 STEF STOF 1 408 c 1 3 STEF STOF 2 104 c 1 3 STEF STOF 2 004 c 1 3 STEF STOF 2 006 c 1 3 STEF STOF 2 406 c 1 3 STEF STOF 2 408 c 1 3 STEF STOF 3 104 c 1 3 STEF STOF 3 004 c 1 3 STEF STOF 3...

Page 9: ...Ventilator Ventilatorkode d mm D Spare parts code Fan Impeller Reservdelskod Fläkthjul Varaosakoodi Puhallinpyörä Varuosa kood Tiivik Ersatzteilkode Laufrad Reservedelskode Ventilatorhjul STEF 1 004 c 6 3 STEF 1 408 c 6 3 STEF 1 406 c 6 3 STEF 2 004 c 6 3 STEF 2 006 c 6 3 STEF 2 408 c 6 3 STEF 2 406 c 6 3 STEF 3 004 c 6 3 STEF 3 006 c 6 3 STEF 3 408 c 6 3 STEF 3 406 c 6 3 STEF 4 004 c 6 3 STEF 4 0...

Page 10: ...004 Signatur Heikki Stenberg Ställning Produktutvecklingschef DECLARATION OF CONFORMITY Manufacturer Fläkt Woods Oy Adress Kalevantie 39 FIN 20520 Turku Finland We declare herewith that Products Roof extraction fan serie type STEF and STOF with accessories a meet the fundamental requirements of the directives below on condition that the mentioned products have been installed in accordance with the...

Page 11: ...11 We reserve the right to make changes Roofmaster STEF and STOF ...

Page 12: ...Fläkt Woods Oy Kalevantie 39 FIN 20520 Turku Finland t 358 20 442 3000 f 358 20 442 3016 w www flaktwoods com STEF STOF GB 06 2004 ...

Reviews: