background image

 

 

1.  With  the  ohmmeter  set  on  its  lowest  scale  take  a 

reading  between  the  top  center  contact  of  the  cell 
and the ionizing fingers on the bottom of the cell. You 
should have continuity. If you do not, then there is a 
bad  contact  between  the  center  contact  and  the  top 
set of ionizing fingers. 

2.  Test  the  resistance  between  the  top  center  contact 

and  the  cell  frame.  You  should  read  infinite 
resistance.  If  not,  you  have  a  short  in  the  ionizing 
section. 

3.  Take a reading between the two outside contacts on 

the top of the cell. You should have continuity. If you 
do  not,  then  there  is  a  bad  contact  between  one  of 
the  contacts  to  the  live  cell  plate.  Test  each  top 
outside  contact  to  the  last  plate  in  the  cell  to 
determine which contact is not mating properly. 

4.  Test the resistance between the outside contacts and 

the cell frame. You should read infinite resistance. If 
not you have a short in the collecting section. 

 

Removing Power Box 

1.  Turn the main system switch 

OFF

 or disconnect the 

power cord. 

2.  Remove the power box cover. 
3.  If  the  unit  does  not  have  a  cord  disconnect  the 

source wires to the Air Cleaner. Cap off the wires so 
the system can still be operated. 

4.  Remove  the  two  nuts  holding  the  power  box  to  the 

cabinet.  

5.  Slide  the  power  box  forward  then  up  to  remove  it 

from the cabinet. 

6.  If  you  are  removing  the  power  box  for  any  length  of 

time tape a cover over the top opening to prevent air 
from entering into the system. 

 
Replacing A Tungsten Ionizing Wire 

Replacement wires are cut to the correct length and 

have eyelets at each end for easy replacement. 
1.  Turn 

OFF

 power to Air Cleaner. 

2.  Remove cell from Air Cleaner. 
3.  Remove  all  parts  of  broken  wire  from  the  cell.  If 

necessary, the cell may be used temporarily with one 
wire missing until a replacement is received. 

4.  Place  one  end  of  the  loop  over  the  finger  at  the 

bottom of the cell.  

5.  Using needle-nose pliers, grip the other end of  wire, 

near  the  bottom  of  the  top  loop.  Pull  the  wire  up 
toward  the  top  finger.  As  you  apply  tension,  the 
bottom finger will give, allowing the placement of the 
loop around the top finger. 

6.  Install cell in Air Cleaner. 
7.  Return power to Air Cleaner. 
8.  Test cell for proper operation. 

10 

Fig. 7 

 Exploded View 

Use Part Numbers When Ordering (See Separate Parts List) 

Part Description 

On/Off Switch 

Safety Interlock Switch 

Performance Indicator Light (Green LED) 

Air Proving Switch 

24 Volt Transformer 

Power Board 

Fibreboard (with 4 Copper Contacts) 

Copper Contact 

Cord Assembly (Optional) 

10  Lid for Power Box 

11  Power Box Complete 

12  Carbon Filters (Set of 3) 

13  Prefilter 

14  Cell Guide (Plastic) 

15  Collecting Cell 

16  Cell Handle 

17  Door (with Plastic Clip & Handle) 

18  Door Handle (Plastic) 

19  Ionizing Wire 

20  Male & Female Door Clip Set 

Summary of Contents for SASD10-2

Page 1: ...i bacteria viruses and more down to 0 01 micron Dual Voltage Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated Carbon Filters remove unpleasant odors Electronic Air Proving Switch for quick wiring optional Dual Indicator Lights show Air Cleaner is working at a glance Galvanized Steel Cabinet for solid vertical or horizontal...

Page 2: ...e of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2 remove all large visible particles such as lint Smaller particles then pass through a two stage electrostatic collecting cell 2 First particles are given a powerful positive electrical charge by the io...

Page 3: ...ir Cleaner will vary with CFM and whether the optional carbon filters have been installed in the unit Location The Air Cleaner must only be installed in the return air duct as close to the fan compartment as possible This location provides the most even airflow across the collecting cells and allows the Air Cleaner to keep the system motor and blower clean The installation can be vertical or horiz...

Page 4: ...ype humidifier must be installed as far from the Air Cleaner as possible 2 Collecting cells must be washed frequently to prevent a mineral deposit build up Installation Location With Air Conditioner Whenever possible the Air Cleaner should be installed upstream of the cooling coil This location will clean the air before it reaches the evaporator coil 4 MODEL DIMENSIONS in cm A B C D E F G H SASD10...

Page 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applicable codes and standards The voltage of the power source must match the voltage indicated on the Air Cleaner The Air Cleaner must operate ONLY when the system fan is running Make sure the Air Cleaner i...

Page 6: ...with DAX Detergent or a non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry tub with water and DAX Detergent and dunk cells up and down until water is dirty 3 Rinse cells well with hot water maximum 120 F 49 C 4 To remove contaminate from the ionizing wires use an old tooth...

Page 7: ...e from the power board Measuring High Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells installed the door closed and the system fan running The Air Cleaner should be on at least 5 minutes to allow voltage to stabilize The cells and ionizing wires must be clean 2 Remove the cover from powe...

Page 8: ...board is turned on and the performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor is properly set down to the bottom of the plastic bushing in the front of the power box To check the APS for proper operation remove the collecting cells turn the unit ON without the fan on The power ...

Page 9: ... voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the high voltage If one is not available this method can be used This will only set an approximate voltage After using this method the voltage should be reset with a high voltage meter as soon as possible 1 Remove power box cover ...

Page 10: ...ove it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system Replacing A Tungsten Ionizing Wire Replacement wires are cut to the correct length and have eyelets at each end for easy replacement 1 Turn OFF power to Air Cleaner 2 Remove cell from Air Cleaner 3 Remove all parts of broken wire from the...

Page 11: ...9 D1 0509 D0 0509 D1 0509 11 Power Box Complete No Cover Depends on options with power box 12 Carbon Filters Set of 3 1156 3 1156 3 1856 3 1856 3 13 Prefilter R0 0855 R1 0855 R2 0855 R8 0855 14 Cell Guide Plastic R1 0603 R1 0603 R1 0603 R1 0603 15 Collecting Cell D0 0400 D1 0400 D2 0400 D8 0400 16 Cell Handle R1 0484 R1 0484 R1 0484 R1 0484 17 Door with Plastic Clip Handle D0 0632 D1 0632 D2 0632 ...

Page 12: ...h needle nose pliers gently pull contacts down or replace contacts Cells arcing excessively power light and per formance indicator light ON or flashing Cells wet from washing Allow cells to dry completely Particles lodged in cell or broken ionizing wire Wash cell Shake particle out of cell Replace wire if necessary Ducts were not cleaned prior to installation of air cleaner Clean ducts Cell plates...

Page 13: ...r basis for the Air Cleaner to function at its peak efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below to keep track of your cleaning schedule DATE CLEANED DATE CLEANED DATE CLEANED 13 ...

Page 14: ...NOTES 14 ...

Page 15: ...anties made in this warranty are exclusive and may not be altered enlarged or changed by any distributor dealer or other person whatsoever FIVE SEASONS COMFORT LIMITED WILL NOT BE RESPONSIBLE FOR 1 Normal maintenance as outlined in the Owner s Manual including cleaning of electronic collecting cells and or replacement of carbon filters 2 Damage or repairs required as a consequence of faulty instal...

Page 16: ...d of the furnace or air handler ensure that there is 220 Volt output from these terminals when the unit is run manually and is running on low speed Some manufacturers do not supply full output voltage to the terminals in the low speed mode so the Air Cleaner will not function The green Performance Indicator Light will not turn on The Air Cleaner performs best when the system fan is on FAN ON or Co...

Reviews: