Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
2-way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
6.7 Re-installation while the outdoor unit need to be repaired
1. Evacuation for
the whole system
Procedure:
1).
Confirm that both the 2-way and 3-way valves are set to the opened position.
2). Connect the vacuum pump to 3-way valve’s service port.
3). Evacuation for approximately one hour. Confirm that the compound meter indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.
Summary of Contents for FSAIF-Pro-123AE2
Page 8: ...8 O optional function ...
Page 13: ...13 5 Wiring Diagram FSAIF Pro 93AE2 FSAIF Pro 183AE2 FSAIF Pro 243AE2 ...
Page 14: ...14 FSAIF Pro 123AE2 ...
Page 15: ...15 5 2 Outdoor Unit FSOAIF Pro 93AE2 ...
Page 16: ...16 FSOAIF Pro 123AE2 ...
Page 17: ...17 FSOAIF Pro 183AE2 ...
Page 18: ...18 FSOAIF Pro 243AE2 ...
Page 61: ...61 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Page 62: ...62 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Page 63: ...63 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Page 64: ...64 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...