background image

Defrost Setting

The defrost timer is located in the wiring box behind the
header panel. In the event a change needs to be made to
the defrost cycles, first DISCONNECT POWER FROM
THE FREEZER. Remove the header panel and the
wiring box. Set the time-of day on the defrost clock and
check to see that the defrost pins are set to the desired
defrost times. The factory settings consist of 3 defrosts
per day (8 a.m., 4 p.m., & 12 a.m.) – Failsafe pin set at 40
minutes.

Do not change failsafe time.

Cabinet Operation

There are two therm-o-discs located on the evaporator
coil. The purpose of one is to keep the evaporator fan
motors and anti-condensate heaters off after defrost
cycles until the coil reaches 32°F (0°C). This prevents
moisture from being pulled down into the product area
and provides faster pull-down. The purpose of the other
control is to de-energize the defrost heater and to ener-
gize the trip solenoid in the time clock to terminate the
defrost cycle when the fin coil reaches 62°F (17°C).
When the refrigeration system first starts up, the room
temperature and the coil temperature are above 62°F
(17°C). The fan delay thermostat is open and the fans
and anti-condensate heaters remain off.

The fan motors will come on when the evaporator temper-
ature is pulled down to approximately 32°F (0°C). This
fan delay control cannot be adjusted. If a single fan motor
fails to start when the thermostat is below 32°F (0°C), it
may be an indication of a defective fan motor. If all fan
motors fail to start, it is an indication of a defective fan
delay control.

10

Operation

Warning

Disconnect the power to unit before
adjusting the defrost timer.

Defrost Timer

Summary of Contents for Isotemp 13-986-327L

Page 1: ...Isotemp General Purpose Laboratory Freezer Catalog Numbers 13 986 327L 327LR 327LA LT2122X1 9 16 09...

Page 2: ...the Cabinet 5 Condensate Pan 6 Electrical Requirements 6 Mounting the Shelves and Display Sensor 7 Cabinet Start Up 7 Thermostat Settings 9 Defrost Setting 10 Operation 10 Maintenance 11 Cleaning the...

Page 3: ...ory operation The unit should be used for its intended application alterations or modifications will void the Warranty This product is not approved for storage of flammable or explosive materials Also...

Page 4: ...r s refusing to honor your damage claim The form required to file such a claim will be supplied by the carrier Concealed Loss or Damage Concealed loss or damage refers to loss or damage which does not...

Page 5: ...e cabinet should be close enough so that no extension cord is needed Installing the Cabinet Whenever possible leave the crate skid on the cabinet until it is moved close to the final position When it...

Page 6: ...he thumbscrew Shut off power supply before plugging in pan supply Electrical Requirements Check the data plate inside the cabinet to be sure the information given matches your requirements Check volt...

Page 7: ...splayed in C Units equipped with chart recorders should have the recorder sensor placed in the glycerol solution with the thermome ter sensor Cabinet Start Up Once the cabinet has been located in its...

Page 8: ...drops below 103 volts when the compressor starts it may indicate that the supply wiring is too small or that the wire run is too long g Make sure that the drain line has not been dis lodged or broken...

Page 9: ...or colder settings counterclockwise for warmer settings There is a stop under the knob to prevent inadvertent turning of the knob too far If the knob reaches the stop before the desired setting is rea...

Page 10: ...e from being pulled down into the product area and provides faster pull down The purpose of the other control is to de energize the defrost heater and to ener gize the trip solenoid in the time clock...

Page 11: ...ere air circulation through the condenser is restricted Condensate Pan Heated This pan is located on the bottom of the cabinet and can be removed for cleaning by removing the screw that holds the cove...

Page 12: ...ept for normal use Inspect the doors often to see that they self close and that the gaskets are in good condition 4 Do not overstock the product in the cabinet which may block normal airflow 5 Keep th...

Page 13: ...g 1 Freezer may be in defrost mode Fans only run when freezer is in refrigeration cycle 2 Door s must be closed 3 Door switch activator plate must depress switch 4 Fan delay switch must be in closed p...

Page 14: ...open until defrost temperature reaches 55 F or higher Make sure thermodisc is closed at beginning of defrost 3 Make sure defrost heaters function The heater should be hot to the touch after freezer ha...

Page 15: ...SPN106110 Door Gasket SPN106111 Bottom Shelf SPN106112 Fan Blade 9 1 2 Dia SPN106117 Defrost Heater HC SPN106118 Switch Key SPN106119 Temperature Control RF1804X362 Digital Thermometer SPN106121 Evap...

Page 16: ...K BLK WHT EVAPORATOR FAN FAN DELAY BRN FACE HEATER BLK DEFROST SWITCH 1 DEFROST SWITCH 2 DEFROST TIMER MOTOR 1 2 X 3 4 N COMPRESSOR MOTOR CONDENSER FAN ORG T STAT ORG ORG WHT DEFROST TERMINATION DEFRO...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...ent is reasonable in the light of the manufacturer s own warranty b The Company shall be released from all obligations under its warranty in the event repairs or modifications are made by persons othe...

Reviews: