The following colour change red/yellow/green is examined as an example for all
colour changes. There are a total of four switch thresholds (S1...S4) in which a
colour change is realised. This leads to the following image without hysteresis.
Risk level
Switching thresholds
Measuring range
RED
RED
YELLOW
YELLOW
GREEN
2
1
0
1
2
S1
S2
S3
S4
Fig. 88:
Colour change (without hysteresis)
The parameter
Col.ch. C1 hyst.
defines a distance to the switch threshold.
The colour change with hysteresis is then realised as follows:
(i) Lower switching thresholds S1 and S2
In case of a colour change from a higher to a lower risk level, the hysteresis
acts with an increasing signal.
S1
+ 0.5
Increasing signal
Falling signal
Fig. 89:
Example: Hysteresis S1
(ii) Upper switching thresholds S3 and S4
In case of a colour change from a lower to a higher risk level, the hysteresis
acts with an decreasing signal.
S4
-0.5
Increasing signal
Falling signal
Fig. 90:
Example: Hysteresis S4
5.5.1.5.4 Colour change C1 delay on
Directory: \Configuration\Channel 1\Colour change C1\Col.ch. C1 delay on
Level 4:
Col.ch. C1 delay on
1
2 3
4
OK Cancel
Edit
0
s
U
Fig. 91:
Colour change C1 delay on
The activation delay acts when changing from a lower risk level to a higher risk
level.