5 | Parameterization
FISCHER Mess- und Regeltechnik GmbH
68 / 88
BA_EN_EA16
5.4.4.4 Menu: Outputs [Level 3]
Menu path: Main menu/Configuration/Outputs/
outputs
Analogue output 1
Analogue output 2
Analogue output 3
Analogue output 4
Level 2
Level 3 (submenu)
MODBUS Slave
Option
Fig. 97:
Menu Outputs
All analogue outputs are configured in the same way. Therefore the associated
parameters are explained below using the example of Analogue output 1.
In units that have a Modbus interface, a further menu appears at the end of the
list to configure the Modbus RTU interface.
Menu: Analogue outp. 1 [Level 4]
Menu path: Main menu/Configuration/Outputs/Analogue output 1/
Analogue outp. 1
Assignment input: 1
Type: Voltage
Level 3
Level 4 (submenu)
3
1
2
Output min.
0.00 V
Input
4
Output max.
10,000V
Input
5
Limit min.
0.000 V
Input
6
Limit max.
10,500V
Input
7
Error signal
10,500V
Input
Fig. 98:
Menu Analogue output 1
Item Value range
Description
1
Assignment input: 1
Assignment input: 2
Assignment input: 3
Assignment input: 4
Assignment input: -
The respective input signal is assigned to
the analogue output 1 with this parameter.
2
Type: Voltage
Type: Current
This parameter is used to define whether
the output signal is of the type current or
voltage. The value range of the following
parameters change depending on how this
is defined.
3
Output min.
0.000 … 10.500V
0.000 … 21.500mA
This parameter is used to define the output
signal that is issued in the measuring range
start of the assigned input signal.