6 Technical data
6.1 General
Please also observe the order code here.
6.2 Input variables
Measuring variable:
Differential pressure for gaseous media
Measuring ranges
Stat. operating pressure
max.
Bursting pressure
0 … 250 mbar
max. 3 bar
> 25 bar
0…1 bar
6.3 Output parameters
Outlet
Signal range
Apparent ohmic resistance
4…20 mA,
3.5…22.5 mA
R
L
≤ (U
b
– 4 V)/0.02 A
6.4 Measurement accuracy
The information refers to a linear, non-spread characteristic curve at 25 C and
applies to all measuring ranges. FS (Full Scale) refers to the basic measuring
range.
Characteristic curve deviation
(Non-linearity and hysteresis)
Maximum:
1.0 % FS
Typical:
0.5 % FS
Temperature coefficient (TK)
Zero point: max. 0.2 % FS / 10 K
Span:
max. 0.2 % FS / 10 K
6.5 Display and control elements
Display
4-digit LC display stating the measuring unit
Keyboard
Foil keypad with 3 buttons
Programming
Damping
0.0 … 100.0 s (jump response time 10 / 90 %) for sig-
nal input
Measuring range unit
mbar, bar, Pa, KPa, PSI and inWc
Start / end of measuring
range
User-definable within the basic measuring range
(1)
Output signal
Adjustable limit values within the signal range
Zero-point stabilising
Zero-point window max. ⅓ of the basic measuring
range
(2)
Zero point correction
±⅓ of the basic measuring range
(3)
Implementation of char-
acteristic curve
Linear, rooted, max. 4:1 spread, inverted
Password
1 ... 999 (0 = no password protection)
(1) Max. effective spread 4:1
(2) measured values around zero are set to zero.
(3) Zero-point correction to compensate different installation positions.
Summary of Contents for DE49 A Series
Page 27: ...FISCHER Mess und Regeltechnik GmbH Attachments 8 BA_EN_DE49_A 27 36 ...
Page 33: ...FISCHER Mess und Regeltechnik GmbH BA_EN_DE49_A 33 36 Notes ...
Page 34: ...FISCHER Mess und Regeltechnik GmbH 34 36 BA_EN_DE49_A Notes ...
Page 35: ...FISCHER Mess und Regeltechnik GmbH BA_EN_DE49_A 35 36 Notes ...