Installation Instructions
AGT 6000 PVMV-N 12V_24V - Chapter B: Installation Instructions
Page 49
B.6 The Battery Monitor - see battery monitor datasheet
For the automatic start of the "AGT" generator a battery monitor is necessary.
This battery monitor ensures that the unit starts automatically when the battery voltage drops
below a pre-set level. If the battery voltage exceeds the adjusted value, then the unit is stopped
automatically. The two contacts of the battery monitor (7+ & 8 -) must connected with the appro-
priate clamps of the automatic control panel (14+ & 13 -).
Responding the battery monitor is indicated by a red light emitting diode. That means if the bat-
tery voltage dropped below the adjustable threshold value, an internal relay is switched on. The
connection occurs with a time delay from approx. 1-3 minutes, voltage drops are ignored e.g.
starting currents.
ATTENTION: - The shut down voltage depends on the battery type and on the battery tempera-
ture. Consider notes or technical data of the respective battery type.
ATTENTION: - Furthermore attention must be paid that the battery shut down voltage of the bat-
tery monitor lies below the synchronised voltage of VCS electronics. The generator runs con-
stantly and cannot be automatically stopped if the synchronised voltage should be less than the
battery shut down voltage.
The the battery monitor may only be connected directly to the terminals of the battery and not to
the output of the generator for example.
B.7 The fan control - see fan control datasheet
Temperature controlled adjustable speed control for one or two stage DC Fan.
The fan regulator must be mounted an a dry and well-aired location. Ensure it is assembled verti-
cally.
The speed adjustment of the fan is determined by the Running Voltage Pulse/Pause modulation.
The Pulse/pause-ratio is goverened by the cooling water temperature via an external NTC-gauge
(terminal 7 and 8). A NTC-resistor reduce his resistor value if the temperature is rising. This NTC-
gauge has the value 100kOhm at 25°C (57°F) and 7kOh m at 70°C (102°F). The full running
voltage is sent to the fan when the upper temperature has been reached.
The fan regulator can be switched on or off by the connection „ON” (terminal 9). The fan control is
switched on, if there is the same voltage to „ON” as „Battery (+)”. If no current flows to „ON”, the
fan control has been switched off. If this option is not required, the circuit board connection „ON”
can be connected direct to „Battery (+)“, via the solder bridge J1.
J1 closed : Fan control continually running
J1 open : Fan control only working if current flows to connection „ON”.
The solder bridge J1 is located directly behind the circuit board fuse when viewed from the main
connection.
Summary of Contents for AGT 6000 PVMV-N
Page 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Page 6: ......
Page 10: ...8 Socket wrench set Hexagon wrench keys ...
Page 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Page 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Page 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Page 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...