Installation Instructions
30.10.12
Kapitel/Chapter 6: Installation Instructions Seite/Page 63
Fig. 6.5.2-3: externer Feinfilter
External fine filter
At generators with Kubota EA 300 or Farymann engines, the
fine filter is delivered with the generator. This fine filter should
be installed in the fuel feed line next to the generator.
representative picture
6.5.3 Connection of the fuel lines at the tank
Note:
General fuel feed and return line must be connected to the
tank at separate connection points.Lead the return fuel pipe
connected to the day tank to the floor
Connection of the return pipe to the tank
The return pipe connected to the tank must be dropped to the same depth as the suction pipe, if the generator is
mounted higher than the tank, in order to prevent fuel running back into the tank after the motor has been switched
off, which can lead to enormous problems, if the generator is switched off for a long period.
Non-return valve in the suction pipe
A non-return valve must be fitted to the suction pipe, which prevents the fuel flowing back after the generator has
been switched off, if it is not possible to use the return flow pipe as a submerge pipe placed in the tank. The instruc-
tions „Bleeding Air from the Fuel System“ must be read after initial operation or after it has stood still for a long
period, in order to preserve the starter battery.
ATTENTION!
Non-return valve for the fuel return pipe
If the fuel tank should be installed over the level of the
generator (e.g. daily tank), then a non-return valve must
be installed into the fuel return pipe to guarantee that
through the return pipe no fuel is led into the injection
pump.
Summary of Contents for 5000i PVK-U
Page 36: ...Seite Page 36 Panda_5000i_PVMV N_Book_eng R02 30 10 12 Leere Seite Intentionally blank Basics...
Page 48: ...The Panda Generator Seite Page 48 Kaptitel Chapter 4 The Panda Generator 30 10 12...
Page 126: ...Generator Tables Seite Page 126 Kaptitel Chapter 8 Generator Tables 30 10 12...
Page 150: ...Page 150 Chapter 11 Installation 30 10 12 Intentionally left blank Installation...
Page 152: ...Page 152 Chapter 12 Maintenance 30 10 12 Intentionally left blank Maintenance...
Page 158: ...Page 158 Chapter 14 Annex 30 10 12 Intentionally left blank Annex...