Maintainence
30.10.12
Kapitel/Chapter 7: Maintainence - Seite/Page 113
Fig. 7.9-2: Air filter matt
Replace the Air filter matt
Close the Air filter housing.
7.10 Trouble shooting
GENERATOR OUTPUT VOLTAGE TOO LOW
If the generator delivers less than 24V current ("undervoltage"), there can be various reasons for this:
Cause
Solution
PGMi is overloaded.
Reduce the electrical load. (Switch off load)
Motor is not reaching the rated rpm.
Refer to "motor faults" section.
MOTOR DOES NOT TURN OVER WHEN STARTING
Cause
Solution
Battery main switch is switched off.
Check the position of the battery main switch, if
necessary switch on..
Battery voltage not sufficient.
Check that connection is firm and whether corrosion
has occurred..
Starting current fault.
The voltage of full batteries fall to a maximum of 11V.
The wiring is severed if the voltage does not drop. The
battery is discharged if the voltage drops further.
MOTOR TURNS OVER BUT DOES NOT START
Cause
Solution
Stop solenoid valve not opening.
Check wire connections and circuitry to solenoid valve.
(ref. DC wiring diagram: Relay K2, Fuse)
Fuel pump does not operate.
Check fuel-filter and pump: clean if necessary.
Lack of fuel.
Check fuel supply.
Glow-plugs not working correctly.
Check glow plugs and heating time.
Summary of Contents for 5000i PVK-U
Page 36: ...Seite Page 36 Panda_5000i_PVMV N_Book_eng R02 30 10 12 Leere Seite Intentionally blank Basics...
Page 48: ...The Panda Generator Seite Page 48 Kaptitel Chapter 4 The Panda Generator 30 10 12...
Page 126: ...Generator Tables Seite Page 126 Kaptitel Chapter 8 Generator Tables 30 10 12...
Page 150: ...Page 150 Chapter 11 Installation 30 10 12 Intentionally left blank Installation...
Page 152: ...Page 152 Chapter 12 Maintenance 30 10 12 Intentionally left blank Maintenance...
Page 158: ...Page 158 Chapter 14 Annex 30 10 12 Intentionally left blank Annex...