Maintainence
Seite/Page 112 - Kaptitel/Chapter 7: Maintainence
30.10.12
Fig. 7.9.1.3-1: Battery
• Measure the electrolyte density of individual cells with a
commercial hydrometer. The hydrometer reading (see table
on following page) indicates the battery’s state of charge.
During measurement, the temperature of the electrolyte
should preferably be 20
C.
Attention
The gases emitted by the battery are explosive! Keep sparks
and naked flames away from the battery!
Do not allow battery acid to come into contact with skin or
clothing!
Wear protective goggles!
Do not rest tools on the battery!
7.9.2 Replacement of the air filter matt
Fig. 7.9-1: Air filter housing
Open the air filter housing by removing the six hexagon screws
Wrench size: SW 8mm
Electrolyte density
in [kg/ l]
Charge status
Normal
Tropical
1.28
1.23
well charged
1.20
1.12
semi-charged, re-charge
1.12
1.08
discharged, immediately charge
Summary of Contents for 5000i PVK-U
Page 36: ...Seite Page 36 Panda_5000i_PVMV N_Book_eng R02 30 10 12 Leere Seite Intentionally blank Basics...
Page 48: ...The Panda Generator Seite Page 48 Kaptitel Chapter 4 The Panda Generator 30 10 12...
Page 126: ...Generator Tables Seite Page 126 Kaptitel Chapter 8 Generator Tables 30 10 12...
Page 150: ...Page 150 Chapter 11 Installation 30 10 12 Intentionally left blank Installation...
Page 152: ...Page 152 Chapter 12 Maintenance 30 10 12 Intentionally left blank Maintenance...
Page 158: ...Page 158 Chapter 14 Annex 30 10 12 Intentionally left blank Annex...